Plan Review Notes
Plan Review Notes For Permit 21041585
Permit Number 21041585
Review Stop G
Sequence Number 3
Notes
Date Text
2021-10-19 16:31:123RD REVIEW FBC-2020 FUEL GAS
 PERMIT- 21041585
 10/19/2021
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE
 1ST AND 2ND REVIEW ARE LISTED BELOW WITH ADDITIONAL
 NOTES IN CAPS FOR FURTHER CLARIFICATION.
  
 1) FAILED ITEMS 1C & G.
  
 C) FAILED. SHEET P2: USING PIPE SIZING TABLE 402.4(4)
 LISTED ON THE PLAN, THE 1-INCH LINE IS UNDERSIZED FOR
 THE 1,046,000 BTU LOAD AT A DEVELOPED LENGTH OF 68 FT.
 ACCORDING TO THE TABLE THE 1-INCH CAN SUPPLY MAXIMUM
 907,000 BTU'S.
  
 G) FAILED. ITEMS 2, 4 & 5. BASED ON THE MANUFACTURER'S
 SPECIFICATIONS REGULATORS ARE REQUIRED FOR THE
 INDIVIDUAL SUPPLY LINES TO THE WATER HEATER AND COOKING
 APPLIANCES. THE RISER SHOWS THE LOW PRESSURE SIDE OF
 THE REGULATOR TO BE 9.5 TO 13 IN.W.C., HOWEVER THE
 SUBMITTED SPECS FOR THE COOKING APPLIANCES ARE
 INDICATING INPUT PRESSURES OF 5 IN.W.C.
 2) FAILED. SHOW THE REQUIRED PIPE UNIONS AT THE
 REGULATORS.
 4) FAILED. REGULATORS ARE REQUIRED FOR THE SUPPLY LINES
 TO THE COOKING APPLIANCES BASED ON THE GAS INPUT
 PRESSURES REQUIRED BY THE APPLIANCE MANUFACTURERS. SHOW
 THE LOCATIONS OF THE REGULATORS IN THE ISOMETRIC
 DRAWING AND PROVIDE VENTING DETAILS IF REQUIRED BY THE
 MANUFACTURER- SECTION- 410.3 FBC FG.
 5) FAILED. THE GASTITE REGULATOR SPECIFIED IS LIMITED
 TO 2 PSI AND THE PLAN INDICATES A 5 PSI SYSTEM. PLEASE
 INDICATE THE MAKE AND MODEL OF THE LOW PRESSURE
 REGULATOR AND SUBMIT SPECS MARKED UP TO SHOW THE INLET
 AND OUTLET PRESSURES AND PIPE SIZES- SECTION 410.2. ON
 THE RISER, PLEASE SHOW THE REQUIRED PIPE UNIONS WITH
 ONE FT. OF EITHER SIDE OF THE REGULATOR- SECTION 410.2
 (7).
  
 2) FAILED. NEW DETAIL E ON P1: PLEASE INDICATE THE TYPE
 AND SIZE OF VENT DUCT AND SUBMIT MANUFACTURER'S
 SPECIFICATIONS FOR THE VENT AND TERMINATION CAP. THE
 SPECS SUBMITTED FOR THE WATER HEATER DO NOT PROVIDE
 VENTING INFORMATION.
  
 3) FAILED. THE SUBMITTED COMBUSTION CALCULATIONS BY
 PAUL ORR P.E. INDICATE A DEFICIENT AMOUNT OF INDOOR
 COMBUSTION AIR FOR THE WATER HEATER AND COOKING
 APPLIANCES, AND THAT ADDITIONAL AIR MUST BE PROVIDED.
 AT THIS TIME NO OTHER MEANS OF SUPPLYING THAT AIR HAS
 BEEN PROVIDED. THE CALC INDICATE 8442.67 CU. FT. OF
 ROOM VOLUME HOWEVER BASED ON THE 1,046,000 BTU LOAD-
 52,300 CU. FT. REQUIRED.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  