| 2021-10-19 16:31:12 | 3RD REVIEW FBC-2020 FUEL GAS |
| | PERMIT- 21041585 |
| | 10/19/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE |
| | 1ST AND 2ND REVIEW ARE LISTED BELOW WITH ADDITIONAL |
| | NOTES IN CAPS FOR FURTHER CLARIFICATION. |
| | |
| | 1) FAILED ITEMS 1C & G. |
| | |
| | C) FAILED. SHEET P2: USING PIPE SIZING TABLE 402.4(4) |
| | LISTED ON THE PLAN, THE 1-INCH LINE IS UNDERSIZED FOR |
| | THE 1,046,000 BTU LOAD AT A DEVELOPED LENGTH OF 68 FT. |
| | ACCORDING TO THE TABLE THE 1-INCH CAN SUPPLY MAXIMUM |
| | 907,000 BTU'S. |
| | |
| | G) FAILED. ITEMS 2, 4 & 5. BASED ON THE MANUFACTURER'S |
| | SPECIFICATIONS REGULATORS ARE REQUIRED FOR THE |
| | INDIVIDUAL SUPPLY LINES TO THE WATER HEATER AND COOKING |
| | APPLIANCES. THE RISER SHOWS THE LOW PRESSURE SIDE OF |
| | THE REGULATOR TO BE 9.5 TO 13 IN.W.C., HOWEVER THE |
| | SUBMITTED SPECS FOR THE COOKING APPLIANCES ARE |
| | INDICATING INPUT PRESSURES OF 5 IN.W.C. |
| | 2) FAILED. SHOW THE REQUIRED PIPE UNIONS AT THE |
| | REGULATORS. |
| | 4) FAILED. REGULATORS ARE REQUIRED FOR THE SUPPLY LINES |
| | TO THE COOKING APPLIANCES BASED ON THE GAS INPUT |
| | PRESSURES REQUIRED BY THE APPLIANCE MANUFACTURERS. SHOW |
| | THE LOCATIONS OF THE REGULATORS IN THE ISOMETRIC |
| | DRAWING AND PROVIDE VENTING DETAILS IF REQUIRED BY THE |
| | MANUFACTURER- SECTION- 410.3 FBC FG. |
| | 5) FAILED. THE GASTITE REGULATOR SPECIFIED IS LIMITED |
| | TO 2 PSI AND THE PLAN INDICATES A 5 PSI SYSTEM. PLEASE |
| | INDICATE THE MAKE AND MODEL OF THE LOW PRESSURE |
| | REGULATOR AND SUBMIT SPECS MARKED UP TO SHOW THE INLET |
| | AND OUTLET PRESSURES AND PIPE SIZES- SECTION 410.2. ON |
| | THE RISER, PLEASE SHOW THE REQUIRED PIPE UNIONS WITH |
| | ONE FT. OF EITHER SIDE OF THE REGULATOR- SECTION 410.2 |
| | (7). |
| | |
| | 2) FAILED. NEW DETAIL E ON P1: PLEASE INDICATE THE TYPE |
| | AND SIZE OF VENT DUCT AND SUBMIT MANUFACTURER'S |
| | SPECIFICATIONS FOR THE VENT AND TERMINATION CAP. THE |
| | SPECS SUBMITTED FOR THE WATER HEATER DO NOT PROVIDE |
| | VENTING INFORMATION. |
| | |
| | 3) FAILED. THE SUBMITTED COMBUSTION CALCULATIONS BY |
| | PAUL ORR P.E. INDICATE A DEFICIENT AMOUNT OF INDOOR |
| | COMBUSTION AIR FOR THE WATER HEATER AND COOKING |
| | APPLIANCES, AND THAT ADDITIONAL AIR MUST BE PROVIDED. |
| | AT THIS TIME NO OTHER MEANS OF SUPPLYING THAT AIR HAS |
| | BEEN PROVIDED. THE CALC INDICATE 8442.67 CU. FT. OF |
| | ROOM VOLUME HOWEVER BASED ON THE 1,046,000 BTU LOAD- |
| | 52,300 CU. FT. REQUIRED. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |