| 2021-09-08 10:00:24 | 2ND REVIEW FBC-2020 PLUMBING |
| | PERMIT- 21041585 |
| | 9/8/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE |
| | 1ST REVIEW ARE LISTED BELOW WITH ADDITIONAL NOTES IN |
| | CAPS FOR FURTHER CLARIFICATION. |
| | |
| | 1) FAILED. SHEET P1: PLEASE PROVIDE A CLEAR SCOPE OF |
| | WORK FOR THE MEN'S AND WOMEN'S RESTROOMS. CLARIFY IF |
| | THE FIXTURES, COMPARTMENT WALLS, LAVATORY COUNTERS, |
| | MIRRORS, DISPENSERS ETC. ARE TO BE REPLACED OR |
| | RELOCATED. PLEASE NOTE THAT THE ENLARGED DIMENSIONED |
| | DRAWINGS WILL BE REQUIRED FOR RECONFIGURED BATHROOMS |
| | AND REPLACEMENT OF COMPARTMENT WALLS. THE CURRENT |
| | CONFIGURATION IN THE MEN'S RESTROOM IS NOT IN |
| | COMPLIANCE WITH SECTION 405.3.4 FBC P- THE WATER CLOSET |
| | BY THE LAVATORY SHALL BE ENCLOSED IN A COMPARTMENT. NEW |
| | ACCESSIBLE PLUMBING FIXTURES ARE BEING INSTALLED IN THE |
| | BATHROOMS WHICH SHALL BE IN COMPLIANCE WITH THE FBC |
| | ACC. PLEASE PROVIDE ENLARGED DRAWINGS AND DETAILS |
| | SHOWING: |
| | |
| | A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE |
| | WATER CLOSETS- SECTION 604.3. |
| | |
| | B) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE |
| | LAVATORIES- SECTION 606.2. |
| | |
| | C) TURNING SPACE DIAMETERS- SECTION 304.3. |
| | |
| | D) CENTERLINES OF THE WATER CLOSETS FROM THE SIDE |
| | WALLS- SECTION 604.2. |
| | |
| | E) HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED |
| | FLOORS- SECTION 604.4. |
| | |
| | F) HEIGHTS OF THE LAVATORY SINK RIMS OR COUNTER |
| | SURFACES FROM THE FINISHED FLOORS- SECTION 606.3. |
| | |
| | G) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SECTION |
| | 606.2 |
| | |
| | IF ACCESSORIES ARE BEING REPLACED PLEASE SHOW: |
| | |
| | H) HEIGHTS OF THE MIRRORS FROM THE FINISHED FLOORS TO |
| | THE REFLECTIVE SURFACES- SECTION 603.3. |
| | |
| | I) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB |
| | BARS FOR THE WATER CLOSETS- SECTION 604.5 & 609.4, |
| | FIGURES 604.5.1 & 604.5.2. |
| | |
| | J) LOCATIONS OF THE WATER CLOSET FLUSH CONTROLS - |
| | SECTION 604.6. |
| | |
| | K) CENTERLINES OF THE TOILET PAPER DISPENSERS MEASURED |
| | FROM THE FRONTS OF THE WATER CLOSETS- SECTION AND |
| | FIGURE 604.7. |
| | |
| | AS REQUESTED IN COMMENT #10 BELOW, PROVIDE FIXTURE |
| | SCHEDULES INDICATING MAKES AND MODELS. |
| | |
| | 2) FAILED. P1 & P2 GREASE WASTE AND INTERCEPTOR: ITEMS |
| | A, B, & C BELOW |
| | |
| | A) FAILED- P1 & P2: PROVIDE GREASE WASTE CALCULATIONS |
| | IN ACCORDANCE WITH SECTION 1003.3.5 OR 1003.3.7 FBC P. |
| | CLEAR WATER WASTE FROM THE HANDSINKS SHALL NOT DRAIN |
| | INTO THE GREASE WASTE LINE AND INTERCEPTOR. PLEASE |
| | REMOVE THE SINKS FROM THE CALCULATIONS- SECTION |
| | 1003.3.1 FBC P. |
| | |
| | B) FAILED- P1 & P2. INDICATE THE SIZE AND TYPE OF |
| | EXISTING GREASE INTERCEPTOR- GRAVITY OR |
| | HYDROMECHANICAL? (1003.3.5 & 1003.3.7) CAPACITY AND |
| | LOCATION OF THE EXISTING GREASE INTERCEPTOR NOT SHOWN. |
| | |
| | C) FAILED- P1 & P2:. THE HAND SINKS AND FLOOR DRAIN IN |
| | THE BEER COOLER SHALL NOT DRAIN INTO THE GREASE WASTE |
| | LINE- SECTION 1003.3.1 FBC P. HANDSINKS ARE NOT |
| | SIGNIFICANT GREASE CONTRIBUTORS, AND THE FLOOR DRAIN IN |
| | THE COOLER SHOULD ONLY BE DRAINING CLEAR WATER WASTE. |
| | THE HANDSINK DRAINAGE HAS BEEN CORRECTED ON THE |
| | DRAWINGS, BUT THE CALCULATIONS NEED TO BE CORRECTED TO |
| | REMOVE THE HANDSINKS. PLEASE NOTE THAT THE FLOOR DRAINS |
| | IN THE COOKING KITCHEN AREA SHALL DRAIN INTO THE GREASE |
| | WASTE LINE AND INTERCEPTOR- SECTION 1003.3.1 FBC P. |
| | |
| | 3) FAILED. P1 & P2: THE HUB DRAIN FOR THE DISHWASHER |
| | SHOWN IN THE ISO IS NOT SHOWN IN THE PLUMBING FLOOR |
| | PLAN-- SECTION 107.2.1 WPB. PLEASE LABEL THE HUB DRAINS |
| | CORRECTLY ON THE FLOOR PLAN- THEY ARE NOT FLOOR DRAINS. |
| | P1 SHOWS FLOOR SINKS AT THE 3-COMPARTMENT SINKS AND |
| | DISHWASHER, P2 SHOWS HUB DRAINS. PLEASE NOTE THAT FLOOR |
| | SINKS ARE INCLUDED IN THE SCHEDULE ON P1. |
| | |
| | 3) FAILED P1 & P2: THE GREASE WASTE DRAIN LINE REQUIRES |
| | NOT LESS THAN ONE VENT PIPE THAT EXTENDS TO THE |
| | OUTDOORS- SECTIONS 904.1 & 918.7 FBC P. THE REVISED |
| | PLAN NOW SHOWS A VTR FOR THE GREASE WASTE LINE BUT NOT |
| | FOR THE SANITARY WHICH IS A SEPARATE SYSTEM AND |
| | REQUIRES THE VTR. |
| | |
| | 4) FAILED. P1 & P2: THE FLOOR DRAINS ARE NOT PROPERLY |
| | VENTED. IT APPEARS A COMBINATION WASTE AND VENT SYSTEM |
| | IS BEING CREATED, HOWEVER THOSE SYSTEMS ARE NOT ALLOWED |
| | FOR GREASE WASTE DRAINS- SECTION 915.1 FBC P. PLEASE |
| | LOCATE VENTS IN THE LINE THAT DO NOT EXCEED THE 12 FT. |
| | MAXIMUM DISTANCE FROM THE FLOOR DRAIN TRAPS- TABLE |
| | 909.1 FBC P. PLEASE NOTE THE AAV'S CAN ONLY BE USED AS |
| | INDIVIDUAL, BRANCH, OR CIRCUIT VENTS- SECTION 918.3 FBC |
| | P. THE FLOOR DRAINS IN THE COOKING AREA OF THE LITCEHN |
| | SHALL DRAIN INTO THE GREASE WASTE LINE AND INTERCEPTOR- |
| | SECTION 1003.3.1. THE CORRECTEDE PLAN SHALL ALSO SHOW |
| | HOW THE FIXTURES ARE TO BE VENTED. |
| | |
| | 6) FAILED. P1 & P2: PROVIDE AN ENLARGED PIPING DRAWING |
| | FOR THE WATER HEATERS SHOWING LOCATIONS OF THERMAL |
| | EXPANSION TANKS, RECIRCULATION PUMPS, SHUTOFF VALVES, |
| | CHECK VALVES, ETC.- SECTIONS 607.2.1.2, 607.3 FBC P. |
| | THE REVISED PLAN SHOWS A NEW RECIRCULATION PUMP IST TO |
| | BE INSTALLED BUT IT IS NOT SHOWN IN THE CORRECT |
| | LOCATION AND NO RECIRCULATION LINE IS SHOWN IN THE |
| | WATER ISOMETRIC. PLEASE ADD THE PUMP TO THE SCHEDULE. |
| | |
| | 7) FAILED. P1 & P2: IT APPEARS THE LENGTHS OF THE HOT |
| | WATER SUPPLY PIPES TO THE LAVATORIES FROM THE WATER |
| | HEATER IS EXCEEDING THE MAXIMUM ALLOWABLE LENGTH AS |
| | INDICATED IN TABLE C404.5.1 FBC EC. EITHER POINT OF USE |
| | WATER HEATERS AT THE LAVATORIES OR A RECIRCULATION PUMP |
| | FOR THE HOT WATER SYSTEM SHALL BE INSTALLED. SEE |
| | COMMENT #6 NOTES ABOVE. |
| | |
| | 8) FAILED. P1 & P2: WHERE HOT WATER IS SUPPLIED TO A |
| | LAVATORY, THE WATER SHALL BE TEMPERED IN ACCORDANCE |
| | WITH SECTIONS 419.5 & 607.1.2 FBC P. PLEASE PROVIDE A |
| | MIXING VALVE THAT CONFORMS TO ASSE 1070. PROVIDE A |
| | PIPING DETAIL ON THE PLAN FOR INSTALLATION. PLEASE ADD |
| | THE WORD LAVATORIES TO NOTE #4 ON P1. CLARIFY IF THE |
| | MIXING VALVES ARE EXISTING OR NEW. |
| | |
| | 9) FAILED P1 & P2: PROVIDE AN INDIRECT WASTE DETAIL FOR |
| | THE 3-COMPARTMENT SINKS- SECTION 802.1.1 FBC P. THE |
| | DETAIL DOES NOT SHOW THE EACH WELL OF THE 3-COMPARTMENT |
| | SINKS DRAINING SEPARATELY INTO THE RECEPTOR. |
| | |
| | 10) FAILED P1 & P2: PLEASE PROVIDE A COMPLETE PLUMBING |
| | FIXTURE SCHEDULE THAT INCLUDES THE DISHWASHER, HUB |
| | DRAINS, FLOOR DRAINS, AND THE REPLACED RESTROOM |
| | FIXTURES- (IF APPLICABLE TO THE SCOPE)- SECTION 107.2.1 |
| | WPB. DISHWASHER, FLOOR SINKS, AND RESTROOM FIXTURES NOT |
| | INCLUDED. |
| | |
| | 11) FAILED. P1: THE PLAN SHOWS ICE MAKERS, ICE BINS, |
| | COOLERS, FROSTER, ETC. WITH NO DRAINS DIRECTLY BELOW |
| | THEM. PLEASE CLARIFY HOW DRAINAGE FROM THESE FIXTURES |
| | WILL BE CONVEYED INTO THE SANITARY SYSTEM. PLEASE NOTE |
| | THAT CLEAR WATER WASTE SHALL NOT DRAIN INTO THE GREASE |
| | WASTE LINE- SECTION 1003.3.1 FBC P. PLEASE REVISE THE |
| | SANITARY ISOMETRIC DRAWING TO MATCH WITH THE FLOOR |
| | PLAN. THERE ARE SEVERAL MISSING FLOOR DRAINS AND DRAIN |
| | LINES. |
| | |
| | 12) FAILED P1 & P2: SHOW AN EXISTING OR NEW CLEANOUT AT |
| | THE JUNCTION OF THE GREASE WASTE LINE AND SEWER |
| | JUNCTION- SECTION 708.1.3 FBC P. LOCATION OF EXISTING |
| | GREASE INTERCEPTOR AND CLEANOUTS NOT SHOWN. |
| | |
| | 13) FAILED P2: PROVIDE A WATER HAMMER ARRESTOR AND |
| | BACKFLOW PREVENTER FOR THE WATER SUPPLY LINE TO THE ICE |
| | MAKER. PLEASE NOTE THAT THIS COMMENT IS APPLICABLE TO |
| | ANY OTHER REQUIRED WATER SUPPLY LINES TO APPLIANCES AND |
| | EQUIPMENT- SECTIONS 604.9 & 608.3 FBC P. REVISE THE |
| | NOTE ON THE ISO TO INCLUDE THE OTHER FIXTURES AND |
| | APPLIANCESAND NOT JUST ON E OF THE ICE BINS. |
| | |
| | 15) FAILED P1 & P2: PROVIDE HOT WATER PIPE INSULATION |
| | SPECIFICATIONS- TABLE C403.2.10 FBC EC. NO INFORMATION |
| | PROVIDED. |
| | |
| | 16) FAILED P1 & P2: INDICATE THE TYPE OF FINISH WALL |
| | AND FLOOR MATERIALS TO BE INSTALLED IN THE RESTROOMS |
| | AND AT THE MOP SINK- SEE SECTIONS 310.3 FBC P AND |
| | 1210.2. FBC B. THE LOCTION OF THE REQUIRED MOP SINK AND |
| | WALL SURROUND MATERIAL NOT PROVIDED. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |