| Date |
Text |
| 2021-09-08 11:19:16 | 2ND REVIEW FBC-2020 FUEL GAS |
| | PERMIT- 21041585 |
| | 9/8/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE |
| | 1ST REVIEW ARE LISTED BEOW WITH ADDITIONAL NOTES IN |
| | CAPS FOR FURTHER CLARIFICATION. |
| | |
| | 1) FAILED. SHEET P2 GAS ISOMETRIC- FBC FG: FAILED ITEMS |
| | A, B, C, D, & G. |
| | |
| | A) FAILED. REMOVE OR CORRECT THE REFERENCE TO TABLE |
| | 1216.2 WHICH IS A TABLE NOT CONTAINED IN THE FBC FG. |
| | THE CORRECT PIPE SIZING TABLE FOR THE 5 PSI SYSTEM WAS |
| | NOT PROVIDED. FOR THE PURPOSES OF THE REVIEW IT IS |
| | ASSUMED THE TABLE USED FOR THE HIGH PRESSURE 1-INCH |
| | GALVANIZED MAIN SUPPLY PIPE IS 402.4(7) 5.0 PSI. THE |
| | TABLE USED FOR THE LOW PRESSURE LINE HAS NOT BEEN |
| | PROVIDED. ACCORDING TO TABLE 402.4(7) THE 1-INCH HIGH |
| | PRESSURE PIPE IS SUFFICIENTLY SIZED. |
| | |
| | B) FAILED. SHOW THE LOCATION OF THE METER AND LABEL IT |
| | AS NEW OR EXISTING- SECTION 402.1. NO INFORMATION |
| | PROVIDED. |
| | |
| | C) FAILED. LIST THE PIPE SIZING TABLE(S) USED IN THE |
| | DESIGN OF THE SYSTEM- SECTION 402.3. SEE COMMENT #1A |
| | NOTES ABOVE. IN ORDER TO PERFORM A COMPLETE REVIEW, THE |
| | LOW PRESSURE SIZING TABLE USED FOR THE SYSTEM MUST BE |
| | PROVIDED. THE RISER IS INDICATING LOW PRESSURE OF 9.5- |
| | 13 IN.W.C. DOWNSTREAM OF THE REGULATOR. PLEASE INDICATE |
| | THE SIZE OF THE SUPPLY PIPE FROM THE REGULATOR TO THE |
| | MOST REMOTE OUTLET. THE DRAWING SHOWS A 1-INCH SLEEVE |
| | BUT NO GAS PIPE SIZE. IT IS ASSUMED A ?-INCH PIPE IS IN |
| | THE SLEEVE WHICH IS UNDERSIZED FOR A TOTAL LOAD OF |
| | 1,046,000 BTUS- SEE SCHED-40 METALLIC LOW PRESSURE |
| | TABLES 402.4(1), 402.4(2), 402.4(3), AND 402.4(4) FBC |
| | FG. |
| | |
| | D) FAILED. PROVIDE THE TOTAL DEVELOPED LENGTH OF THE |
| | SYSTEM FROM THE METER TO THE MOST REMOTE OUTLET, AND |
| | THE INDIVIDUAL CUT PIPE AND BRANCH LENGTH MEASUREMENTS- |
| | SECTION 402.4.1. PROVIDE THE TOTAL AND INDIVIDUAL HIGH |
| | PRESSURE AND LOW PRESSURE RUN LENGTHS. |
| | |
| | G) FAILED. SHOW REQUIRED SHUTOFF VALVES, REGULATORS, |
| | AND PIPE UNIONS ON THE BRANCH LINES TO THE APPLIANCES- |
| | SECTIONS 409.1 & 410.1. 1) TYPICAL SHUTOFF VALVES ARE |
| | MISLABELED AS FV (FIRE VALVES)- PLEASE CORRECT. 2) SHOW |
| | THE REQUIRED PIPE UNIONS AT THE REGULATOR. 3) SHOW THE |
| | LOCATION OF THE REQUIRED AUTOMATIC GAS SHUTOFF VALVE |
| | FOR THE COOKING APPLIANCES TO BE CONNECTED TO THE FIRE |
| | SUPPRESSION SYSTEM- SEC. 10.4.1 NFPA 96. PLEASE NOTE |
| | THE VALVES SHALL BE BELOW THE CEILING AND ACCESSIBLE. |
| | 4) PLEASE NOTE THAT REGULATORS MAY BE REQUIRED FOR THE |
| | SUPPLY LINES TO THE COOKING APPLIANCES BASED ON THE GAS |
| | INPUT PRESSURES REQUIRED BY THE APPLIANCE |
| | MANUFACTURERS. 5) PLEASE INDICATE THE MAKE AND MODEL OF |
| | THE LOW PRESSURE REGULATOR AND SUBMIT SPECS MARKED UP |
| | TO SHOW THE INLET AND OUTLET PRESSURES AND PIPE SIZES- |
| | SECTION 410.2. ON THE RISER, PLEASE SHOW THE REQUIRED |
| | PIPE UNIONS WITH ONE FT. OF EITHER SIDE OF THE |
| | REGULATOR- SECTION 410.2 (7). |
| | |
| | 2) FAILED. PROVIDE THE MAKE AND MODEL OF THE NEW |
| | TANKLESS WATER HEATER ON THE PLAN AND SUBMIT |
| | MANUFACTURER'S SPECIFICATIONS- SECTION 624.1 FBC FG. |
| | THE WATER HEATER LOCATED IN THE INDOORS WILL REQUIRE |
| | COMBUSTION AIR AND A VENTING SYSTEM. PLEASE PROVIDE |
| | COMBUSTION AIR CALCULATIONS IN COMPLIANCE WITH SECTION |
| | 304.1 FBC FG, AND A VENTING DIAGRAM AND VENT |
| | SPECIFICATIONS- SECTION 503.1 FBC FG. VENTING DIAGRAM |
| | NOT PROVIDED. SEE COMBUSTION AIR COMMENT #3 BELOW. |
| | |
| | 3) FAILED. PROVIDE COMBUSTION AIR CALCULATIONS FOR THE |
| | COOKING APPLIANCES AND INDICATE HOW THE AIR IS BEING |
| | PROVIDED- SECTION 304.1 FBC FG. THE SUBMITTED |
| | COMBUSTION CALCULATIONS BY PAUL ORR P.E. INDICATE A |
| | DEFICIENT AMOUNT OF INDOOR COMBUSTION AIR FOR THE WATER |
| | HEATER AND COOKING APPLIANCES, AND THAT ADDITIONAL AIR |
| | MUST BE PROVIDED. AT THIS TIME NO OTHER MEANS OF |
| | SUPPLYING THAT AIR HAS BEEN PROVIDED. |
| | |
| | 4) FAILED. SUBMIT MANUFACTURER'S FOR THE COOKING |
| | APPLIANCES- SECTION 623.1 FBC FG. NOT PROVIDED. THE |
| | SUBMITTALS MAY BE DEFERRED IN ACCORDANCE WITH SECTION |
| | 107.3.4.1 WPB AMENDMENTS TO THE FBC. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | CCOLE@WPB |
| | |