Plan Review Notes
Plan Review Notes For Permit 21041585
Permit Number 21041585
Review Stop P
Sequence Number 1
Notes
Date Text
2021-06-15 11:11:091ST REVIEW FBC-2020 PLUMBING
 PERMIT- 21041585
 6/15/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P1: PLEASE PROVIDE A CLEAR SCOPE OF WORK FOR
 THE MEN'S AND WOMEN'S RESTROOMS. CLARIFY IF THE
 FIXTURES, COMPARTMENT WALLS, LAVATORY COUNTERS,
 MIRRORS, DISPENSERS ETC. ARE TO BE REPLACED OR
 RELOCATED. PLEASE NOTE THAT THE ENLARGED DIMENSIONED
 DRAWINGS WILL BE REQUIRED FOR RECONFIGURED BATHROOMS
 AND REPLACEMENT OF COMPARTMENT WALLS. THE CURRENT
 CONFIGURATION IN THE MEN'S RESTROOM IS NOT IN
 COMPLIANCE WITH SECTION 405.3.4 FBC P- THE WATER CLOSET
 BY THE LAVATORY SHALL BE ENCLOSED IN A COMPARTMENT.
  
 2) P1 & P2 GREASE WASTE AND INTERCEPTOR:
 A) PROVIDE GREASE WASTE CALCULATIONS IN ACCORDANCE WITH
 SECTION 1003.3.5 OR 1003.3.7 FBC P.
 B) INDICATE THE SIZE AND TYPE OF EXISTING GREASE
 INTERCEPTOR- GRAVITY OR HYDROMECHANICAL? (1003.3.5 &
 1003.3.7)
 C) THE HAND SINKS AND FLOOR DRAIN IN THE BEER COOLER
 SHALL NOT DRAIN INTO THE GREASE WASTE LINE- SECTION
 1003.3.1 FBC P. HANDSINKS ARE NOT SIGNIFICANT GREASE
 CONTRIBUTORS, AND THE FLOOR DRAIN IN THE COOLER SHOULD
 ONLY BE DRAINING CLEAR WATER WASTE.
  
 3) P1 & P2: THE HUB DRAIN FOR THE DISHWASHER SHOWN IN
 THE ISO IS NOT SHOWN IN THE PLUMBING FLOOR PLAN--
 SECTION 107.2.1 WPB. PLEASE LABEL THE HUB DRAINS
 CORRECTLY ON THE FLOOR PLAN- THEY ARE NOT FLOOR DRAINS.
  
 3) P1 & P2: THE GREASE WASTE DRAIN LINE REQUIRES NOT
 LESS THAN ONE VENT PIPE THAT EXTENDS TO THE OUTDOORS-
 SECTIONS 904.1 & 918.7 FBC P.
  
 4) P1 & P2: THE FLOOR DRAINS ARE NOT PROPERLY VENTED.
 IT APPEARS A COMBINATION WASTE AND VENT SYSTEM IS BEING
 CREATED, HOWEVER THOSE SYSTEMS ARE NOT ALLOWED FOR
 GREASE WASTE DRAINS- SECTION 915.1 FBC P. PLEASE LOCATE
 VENTS IN THE LINE THAT DO NOT EXCEED THE 12 FT. MAXIMUM
 DISTANCE FROM THE FLOOR DRAIN TRAPS- TABLE 909.1 FBC P.
 PLEASE NOTE THE AAV'S CAN ONLY BE USED AS INDIVIDUAL,
 BRANCH, OR CIRCUIT VENTS- SECTION 918.3 FBC P.
  
 5) P1 & P2: PLEASE PROVIDE AN EQUIPMENT SCHEDULE FOR
 THE NEW TANKLESS WATER HEATER SUBMIT MANUFACTURER'S
 SPECIFICATIONS- SECTION 624.1 FBC FG ( SEE SEPARATE
 FUEL GAS REVIEW COMMENTS).
  
 6) P1 & P2: PROVIDE AN ENLARGED PIPING DRAWING FOR THE
 WATER HEATERS SHOWING LOCATIONS OF THERMAL EXPANSION
 TANKS, RECIRCULATION PUMPS, SHUTOFF VALVES, CHECK
 VALVES, ETC.- SECTIONS 607.2.1.2, 607.3 FBC P.
  
 7) P1 & P2: IT APPEARS THE LENGTHS OF THE HOT WATER
 SUPPLY PIPES TO THE LAVATORIES FROM THE WATER HEATER IS
 EXCEEDING THE MAXIMUM ALLOWABLE LENGTH AS INDICATED IN
 TABLE C404.5.1 FBC EC. EITHER POINT OF USE WATER
 HEATERS AT THE LAVATORIES OR A RECIRCULATION PUMP FOR
 THE HOT WATER SYSTEM SHALL BE INSTALLED.
  
 8) P1 & P2: WHERE HOT WATER IS SUPPLIED TO A LAVATORY,
 THE WATER SHALL BE TEMPERED IN ACCORDANCE WITH SECTIONS
 419.5 & 607.1.2 FBC P. PLEASE PROVIDE A MIXING VALVE
 THAT CONFORMS TO ASSE 1070. PROVIDE A PIPING DETAIL ON
 THE PLAN FOR INSTALLATION.
  
 9) P1 & P2: PROVIDE AN INDIRECT WASTE DETAIL FOR THE
 3-COMPARTMENT SINKS- SECTION 802.1.1 FBC P.
  
 10) P1 & P2: PLEASE PROVIDE A COMPLETE PLUMBING FIXTURE
 SCHEDULE THAT INCLUDES THE DISHWASHER, HUB DRAINS,
 FLOOR DRAINS, AND THE REPLACED RESTROOM FIXTURES- (IF
 APPLICABLE TO THE SCOPE)- SECTION 107.2.1 WPB.
  
 11) P1: THE PLAN SHOWS ICE MAKERS, ICE BINS, COOLERS,
 FROSTER, ETC. WITH NO DRAINS DIRECTLY BELOW THEM.
 PLEASE CLARIFY HOW DRAINAGE FROM THESE FIXTURES WILL BE
 CONVEYED INTO THE SANITARY SYSTEM. PLEASE NOTE THAT
 CLEAR WATER WASTE SHALL NOT DRAIN INTO THE GREASE WASTE
 LINE- SECTION 1003.3.1 FBC P.
  
 12) P1 & P2: SHOW AN EXISTING OR NEW CLEANOUT AT THE
 JUNCTION OF THE GREASE WASTE LINE AND SEWER JUNCTION-
 SECTION 708.1.3 FBC P.
  
 13) P2: PROVIDE A WATER HAMMER ARRESTOR AND BACKFLOW
 PREVENTER FOR THE WATER SUPPLY LINE TO THE ICE MAKER.
 PLEASE NOTE THAT THIS COMMENT IS APPLICABLE TO ANY
 OTHER REQUIRED WATER SUPPLY LINES TO APPLIANCES AND
 EQUIPMENT- SECTIONS 604.9 & 608.3 FBC P.
  
 14) P1 & P2: PLEASE PROVIDE CODE DATA AND A SYMBOL
 LEGEND ON THE PLAN- SECTION 107.2.1 WPB.
  
 15) P1 & P2: PROVIDE HOT WATER PIPE INSULATION
 SPECIFICATIONS- TABLE C403.2.10 FBC EC.
  
 16) P1 & P2: INDICATE THE TYPE OF FINISH WALL AND FLOOR
 MATERIALS TO BE INSTALLED IN THE RESTROOMS AND AT THE
 MOP SINK- SEE SECTIONS 310.3 FBC P AND 1210.2. FBC B.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  