2021-06-11 11:55:201ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21041585
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) ACCORDING TO OUR RECORDS THIS APPEARS TO BE A CHANGE
 OF USE FROM RETAIL TO A-2. IF THIS IS NOT A CHANGE OF
 USE PLEASE PRESENT DOCUMENTATION THAT IT WAS CHANGED
 FROM RETAIL TO A-2.
  
 2) PLEASE PROVIDE A MECHANICAL DEMO DRAWING. WITHOUT
 THIS I CANNOT COMPLETE THE REVIEW AND THERE MAY BE
 ADDITIONAL COMMENTS ON THE NEXT CYCLE. FBC 107.2.1
  
 3) PLEASE PROVIDE AN OUTDOOR AIR CALCULATION FOR EACH
 USE OF SPACE IN ACCORDANCE WITH FBC M 403.3.1.1 AND
 TABLE 403.3.1.1 AND NOT BY THE ARCHITECTURAL OCCUPANT
 COUNT.
  
 4) PLEASE PUT A NOTE ON THE MECHANICAL DRAWING THAT
 STATES THE HOOD AND GREASE DUCT WILL NOT BE REVIEWED
 UNDER THIS PERMIT AS IT WILL REQUIRE A SEPARATE PERMIT
 AND MECHANICAL REVIEW.
  
 5) PLEASE PUT A NOTE ON THE MECHANICAL DRAWING THAT
 STATES THE REFRIGERATION WILL NOT BE REVIEWED UNDER
 THIS PERMIT AS IT WILL REQUIRE A SEPARATE PERMIT AND
 MECHANICAL REVIEW.
  
 6) PLEASE CORRECT THE SCOPE TO REPRESENT THE WORK BEING
 COMPLETED UNDER THIS PERMIT AS THERE IS NEW DUCTWORK
 BEING ADDED TO THE EXISTING TRUNK LINE.
  
 7) PLEASE PROVIDE AN EQUIPMENT SIZING CALCULATIONS. FBC
 EC 403.2.1
  
 8) PLEASE PROVIDE INFORMATION ON THE EXISTING
 MECHANICAL UNITS TO VERIFY THE CFM?S. FBC 107.2.1
  