| 2021-06-11 11:55:20 | 1ST REVIEW FBC-2020 MECHANICAL |
| | PERMIT-21041585 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE |
| | FBC M- FLORIDA MECHANICAL CODE |
| | FBC EC- FLORIDA ENERGY CONSERVATION |
| | FBC FG- FLORIDA FUEL GAS |
| | FBC EX- FLORIDA EXISTING BUILDING CODE |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) ACCORDING TO OUR RECORDS THIS APPEARS TO BE A CHANGE |
| | OF USE FROM RETAIL TO A-2. IF THIS IS NOT A CHANGE OF |
| | USE PLEASE PRESENT DOCUMENTATION THAT IT WAS CHANGED |
| | FROM RETAIL TO A-2. |
| | |
| | 2) PLEASE PROVIDE A MECHANICAL DEMO DRAWING. WITHOUT |
| | THIS I CANNOT COMPLETE THE REVIEW AND THERE MAY BE |
| | ADDITIONAL COMMENTS ON THE NEXT CYCLE. FBC 107.2.1 |
| | |
| | 3) PLEASE PROVIDE AN OUTDOOR AIR CALCULATION FOR EACH |
| | USE OF SPACE IN ACCORDANCE WITH FBC M 403.3.1.1 AND |
| | TABLE 403.3.1.1 AND NOT BY THE ARCHITECTURAL OCCUPANT |
| | COUNT. |
| | |
| | 4) PLEASE PUT A NOTE ON THE MECHANICAL DRAWING THAT |
| | STATES THE HOOD AND GREASE DUCT WILL NOT BE REVIEWED |
| | UNDER THIS PERMIT AS IT WILL REQUIRE A SEPARATE PERMIT |
| | AND MECHANICAL REVIEW. |
| | |
| | 5) PLEASE PUT A NOTE ON THE MECHANICAL DRAWING THAT |
| | STATES THE REFRIGERATION WILL NOT BE REVIEWED UNDER |
| | THIS PERMIT AS IT WILL REQUIRE A SEPARATE PERMIT AND |
| | MECHANICAL REVIEW. |
| | |
| | 6) PLEASE CORRECT THE SCOPE TO REPRESENT THE WORK BEING |
| | COMPLETED UNDER THIS PERMIT AS THERE IS NEW DUCTWORK |
| | BEING ADDED TO THE EXISTING TRUNK LINE. |
| | |
| | 7) PLEASE PROVIDE AN EQUIPMENT SIZING CALCULATIONS. FBC |
| | EC 403.2.1 |
| | |
| | 8) PLEASE PROVIDE INFORMATION ON THE EXISTING |
| | MECHANICAL UNITS TO VERIFY THE CFM?S. FBC 107.2.1 |
| | |