| 2021-06-15 11:50:55 | 1ST REVIEW FBC-2020 FUEL GAS |
| | PERMIT- 21041585 |
| | 6/15/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET P2 GAS ISOMETRIC- FBC FG: |
| | A) REMOVE OR CORRECT THE REFERENCE TO TABLE 1216.2 |
| | WHICH IS A TABLE NOT CONTAINED IN THE FBC FG. |
| | B) SHOW THE LOCATION OF THE METER AND LABEL IT AS NEW |
| | OR EXISTING- SECTION 402.1 |
| | C) LIST THE PIPE SIZING TABLE(S) USED IN THE DESIGN OF |
| | THE SYSTEM- SECTION 402.3. |
| | D) PROVIDE THE TOTAL DEVELOPED LENGTH OF THE SYSTEM |
| | FROM THE METER TO THE MOST REMOTE OUTLET, AND THE |
| | INDIVIDUAL CUT PIPE AND BRANCH LENGTH MEASUREMENTS- |
| | SECTION 402.4.1. |
| | E) SHOW THE WATER HEATER AND THE BRANCH PIPE TO IT- |
| | SECTION 402.3. |
| | F) INDICATE THE TYPE AND SIZE OF PIPE SLEEVE- SECTION |
| | 404.8.1. |
| | G) SHOW REQUIRED SHUTOFF VALVES, REGULATORS, AND PIPE |
| | UNIONS ON THE BRANCH LINES TO THE APPLIANCES- SECTIONS |
| | 409.1 & 410.1. |
| | |
| | 2) PROVIDE THE MAKE AND MODEL OF THE NEW TANKLESS WATER |
| | HEATER ON THE PLAN AND SUBMIT MANUFACTURER'S |
| | SPECIFICATIONS- SECTION 624.1 FBC FG. THE WATER HEATER |
| | LOCATED IN THE INDOORS WILL REQUIRE COMBUSTION AIR AND |
| | A VENTING SYSTEM. PLEASE PROVIDE COMBUSTION AIR |
| | CALCULATIONS IN COMPLIANCE WITH SECTION 304.1 FBC FG, |
| | AND A VENTING DIAGRAM AND VENT SPECIFICATIONS- SECTION |
| | 503.1 FBC FG. |
| | |
| | 3) PROVIDE COMBUSTION AIR CALCULATIONS FOR THE COOKING |
| | APPLIANCES AND INDICATE HOW THE AIR IS BEING PROVIDED- |
| | SECTION 304.1 FBC FG. |
| | |
| | 4) SUBMIT MANUFACTURER'S FOR THE COOKING APPLIANCES- |
| | SECTION 623.1 FBC FG. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |