| 2021-06-08 21:13:07 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. EXISTING SERVICE NOT SHOWN, SHOW SERVICE SIZE AND |
| | RISER DIAGRAM. NEC 215.5; WPB FBC 107.2.1 |
| | |
| | 2. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL |
| | LOADS. SEVERAL APPLIANCES AND SPECFIC LOADS SHOWN IN |
| | PANEL SCHEDULE ARE NOT SHOWN IN "LOAD CALCULATION" |
| | PROVIDED. NEC 220 NEC 220.14A |
| | |
| | 3. WHAT IS VOLTAGE OF SERVICE? PANEL B SHOWS 120/240V |
| | 3PH 4W WHICH WOULD BE A DELTA SYSTEM WITH A "HI-LEG". |
| | PANEL A IS SHOWN AS 120/240V SINGLE-PHASE. |
| | |
| | 4. NOTE 17 IN ELECTRICAL NOTES STATE LV TO BE INSTALLED |
| | FOR TV'S AND CAT 6 FOR DATA BUT NOT SHOWN ON PLAN??? |
| | PROVIDE CORRECTION. FBC 107.2.1 |
| | |
| | 5. NOTE 21 STATES PRE-WIRE FOR SPEAKERS BUT NOTHING |
| | SHOWN ON PLAN??? PROVIDE CORRECTION FBC 107.2.1 |
| | |
| | 6. SHOW WINDOW RECEPTACES ARE ON PANEL SCHEDULE BUT NOT |
| | SHOWN ON PLAN? FBC 107.2.1 NEC 210.62 |
| | |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | CODES IN EFFECT: |
| | |
| | HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B |
| | UILDING-PERMIT-FORMS |
| | |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2020 7TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| | 7TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |
| | FRANK GIAQUINTO III |
| | ELECTRICAL INSPECTOR |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | [email protected] |
| | CELL: 561-805-6744 |
| | |