| 2021-05-05 14:31:35 | 05/05/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. THERE IS A GAS HEATER SHOWN. YOU MAY CHOOSE TO HAVE |
| | A GAS REVIEW DONE THIS TIME AND MUST-HAVE INFORMATION |
| | AND DOCUMENTS SUBMITTED. THIS WILL HAVE THE GAS APPROVE |
| | FOR A SUB PERMIT, OR IF YOU DECIDED NOT TO, PLEASE PUT |
| | A NOTE NEXT TO THE GAS HEATER ( A SEPARATE PERMIT BY A |
| | LICENSED CONTRACTOR FOR THE GAS SYSTEM). AN N WILL BE |
| | PLACED ON THIS REVIEW, WHICH STANDS FOR NOT REQUIRED |
| | BUT, A SUB PERMIT WON'T BE ISSUED UNIT A REVIEW IS DONE |
| | FOR THAT SUB PERMIT, SO PLEASE BE ADVISED ON THIS |
| | PROCEDURE. |
| | |
| | 2. ON SHEET P101; |
| | A. IT SHOWS A SHOWER OUTSIDE THAT IS CONNECTED TO THE |
| | SANITARY. STORMWATER SHALL NOT BE DRAINED INTO SEWERS |
| | INTENDED FOR SEWAGE ONLY PER THE 2020 FBC P 1101.3 |
| | PROHIBITED DRAINAGE. IT MAY DRAIN TO A DRY WELL OR A |
| | NEARBY LOCATION, SO PLEASE GIVE DETAIL OF A DRY WELL OR |
| | NOTE THE LOCATION. |
| | |
| | B. IT SHOWS ON PLANS A TANK-LESS WATER HEATER; PLEASE |
| | INDICATE THE LOCATION AND DISTANCE OF ANY OPERABLE |
| | DOORS OR WINDOWS IN RELATION TO THE WATER HEATER. THE |
| | LOCATION OF THE WATER HEATER SHALL COMPLY WITH THE |
| | MANUFACTURER'S INSTALLATION INSTRUCTIONS PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1. INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION, |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| | |
| | LUIS A. CRESPO |
| | PLUMBING PLAN EXAMINER / INSPECTOR |
| | EMAIL: [email protected] OFFICE: 561 805-6720 |
| | |