| 2021-05-11 13:42:17 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT-21041525 |
| | 5/11/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) P1: THE COLD-WATER BRANCH LINES SERVING EACH WATER |
| | HEATER SHALL BE PROVIDED WITH DEDICATED SHUT OFF |
| | VALVES- SECTION 503.1 FBC P. |
| | |
| | 2) P1: PROVIDE A PLUMBING FIXTURE SCHEDULE- SECTIONS |
| | 410.1 & 418.1 FBC P. |
| | |
| | 3) D-1 & P1: SHOW AREAS OF SLAB DEMOLITION AND PROVIDE |
| | A SLAB REPAIR DETAIL- SECTION 107.2.1 WPB. |
| | |
| | 4) A1 & A2: SHOW THE 30X48 INCH CLEAR FLOOR SPACE |
| | DIAGRAMS AND DIMENSIONS FOR THE NEW SINKS- SECTIONS |
| | 606.2 & 305.1 FBC ACC. |
| | |
| | 5) A2: PROVIDE ELEVATION DRAWINGS FOR THE NEW SINKS |
| | THAT ARE COMPLIANT WITH FIGURE 306.3 FBC ACC. |
| | |
| | 6) A2 DRINKING FOUNTAIN DETAIL: SHOW THE SPOUT HEIGHT |
| | OF THE HI (STANDING PERSONS) DRINKING FOUNTAIN- SECTION |
| | 602.7 FBC ACC. |
| | |
| | 7) A1 & A2: INDICATE HOW THE DRINKING FOUNTAIN WILL BE |
| | INSTALLED IN COMPLIANCE WITH SECTION 307.1 PROTRUDING |
| | OBJECTS FBC ACC. |
| | |
| | 8) A1 & A2: INDICATE HOW THE WALLS SURROUNDING THE MOP |
| | SINK WILL BE FINISHED IN COMPLIANCE WITH SECTION |
| | 1210.2.2 FBC B. |
| | WALLS AND PARTITIONS WITHIN 2 FEET OF SERVICE SINKS, |
| | URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH, HARD, |
| | NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS THAN 4 |
| | FEET ABOVE THE FLOOR, AND EXCEPT FOR STRUCTURAL |
| | ELEMENTS, THE MATERIALS USED IN SUCH WALLS SHALL BE OF |
| | A TYPE THAT IS NOT ADVERSELY AFFECTED BY MOISTURE. |
| | PLEASE NOTE THAT PAINTED DRYWALL IS NOT CONSIDERED A |
| | HARD, NON-ABSORBENT SURFACE. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |