| Plan Review Notes For Permit 21041525 |
| Permit Number |
21041525 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-05-12 09:00:10 | OFFICE BUILDOUT | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected]. | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) PLEASE SHOW THE CORRIDOR WALLS FIRE RATING TO COMPLY | | | WITH FBC TABLE 1020.1 | | | 2) PLEASE SHOW THE CORRIDOR FIRE PARTITION CONTINUITY | | | TO COMPLY WITH FBC 708.4 | | | 3) PLEASE SHOW THE CORRIDOR WALL DOORS AND GLAZING FIRE | | | RATINGS TO COMPLY WITH FBC 716 | | | 4) PLEASE SHOW FIRE RATED DOORS TO AUTOMATICALLY CLOSE | | | AND LATCH PER FBC 716.5.9 | | | 5) PLEASE SHOW THE LOCATION OF THE REQUIRED EXIT SIGNS | | | OVER THE 2ND EXIT LOCATION (BREAKROOM DOOR AND EXIT | | | ACCESS DOOR FROM THE BREAK ROOM) FBC 1013 | | | 6) PLEASE SHOW THE EXIT ACCESS DOOR FROM THE BREAK ROOM | | | TO SWING IN THE DIRECTION OF EGRESS WITHOUT BECOMING AN | | | ENCROACHMENT TO THE EXIT ACCESS CORRIDOR OUTSIDE THE | | | DOOR FBC 1010.1.2.1 AND FBC 1005.7 | | | 7) PLEASE SHOW WALL FINISH AT MOP/SERVICE SINK TO | | | COMPLY WITH FBC 1210.2.2 (DRYWALL IS NOT CONSIDERED A | | | HARD SURFACE) | | | 8) BUILDING CONSTRUCTION TYPE SHOWN AS (IV) - PLEASE RE | | | EVALUATE THE BUILDING CONSTRUCTION TYPE - (IV) IS HEAVY | | | TIMBER. | | | |
|