Plan Review Notes
Plan Review Notes For Permit 21041463
Permit Number 21041463
Review Stop P
Sequence Number 1
Notes
Date Text
2021-05-12 16:31:001ST REVIEW FBC-2020 RES. PLUMBING.
 PERMIT- 21041463
 5/12/2021
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) A-1 & S-1: THE PLUMBING RISER DOES NOT INCLUDE THE
 NEW KITCHEN SINK- SECTION 107.3.5.3 WPB.
  
 2) A-1: PROVIDE THE MAKE, MODEL NUMBER, GALLON SIZE,
 AND EFFICIENCY RATING OF THE NEW WATER HEATER- TABLE
 C404.2 FBC EC. CLARIFY IF THE WATER IS ELECTRIC OR
 GAS-FIRED- SECTION 107.2.1 WPB.
  
 3) A-1: PROVIDE A SHOWER PAN DETAIL- SECTION P2709.1 &
 P2709.2 FBC RES.
  
 4) A-1: INDICATE HOW WATER WILL BE PROVIDED TO THE
 GUEST HOUSE- SECTION P2602.1 FBC RES.
  
 5) PLEASE NOTE THAT TWO SEPARATELY ADDRESSED DWELLING
 UNITS ON THE SAME LOT MAY REQUIRE INSTALLATION OF A
 BACKFLOW PREVENTION ASSEMBLY AT THE POINT OF DELIVERY.
 THE TYPE OF BACKFLOW ASSEMBLY REQUIRED WILL BE
 DEPENDENT UPON THE DEGREE OF HAZARD POSED BY THE WATER
 USER. A REDUCED PRESSURE ZONE BACKFLOW DEVICE WILL BE
 NEEDED FOR THE WATER METER PER THE CITY OF WEST PALM
 CROSS UTILITIES DEPARTMENT AND THEIR CONNECTION CONTROL
 PROGRAM. PLEASE NOTE THAT A FL. LICENSED PLUMBING
 CONTRACTOR SHALL OBTAIN A SEPARATE PERMIT FOR
 INSTALLATION OF THE BACKFLOW PREVENTER IN ACCORDANCE
 WITH SECTION 105.1 WPB AND SEC. 90-33 WPB CODE OF
 ORDINANCES. THE DEVICE SHALL BE TESTED AND CERTIFIED BY
 THE WPB UTILITIES DEPARTMENT PRIOR TO FINAL INSPECTION
 BY THE BUILDING DEPARTMENT. PLEASE CONTACT THE WPB
 UTILITIES CENTRAL OPERATIONS DEPT.AT 561-822-2210 FOR
 FURTHER INFORMATION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  