2021-05-11 17:29:09ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) PLEASE SUBMIT RISER SHOWING MAIN AND GROUNDING 215.5
  
 2) NO SMOKE ALARM(S) SHOWN R314 FBC 2020
  
 3) OUTLET REQUIRED AT THE REAR OF THE UNIT. 210.52
  
 4) LIGHT REUIRED WHERE AC AIR HANDLER IS INSTALLED
 ABOVE CEILING 210.70
  
 5) OUTLET REQUIRED FOR AC AIR HANDLER INSTSLLED ABOVE
 CEILING 210.53