| Plan Review Notes For Permit 21041449 |
| Permit Number |
21041449 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2021-06-29 07:02:07 | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC 2020 RESIDENTIAL 301: | | | | | | 1. THE INSTALLATION SCHEDULE DOES NOT STATE WHAT THE | | | SUBSTRATE IS - BLOCK, CONCRETE? IS THE SUBSTRATE THE | | | SAME TOP AND BOTTOM? | | | | | | WITHOUT THIS INFORMATION, IT IS NOT POSSIBLE TO | | | COMPLETE THE REVIEW. | | | | | | NEW COMMENT: | | | | | | 2. THE "OPENING SIZE" COLUMN SHOULD BE WIDTH X HEIGHT. | | | SINCE THE PROPOSED SHUTTERS ARE ACCORDION, THE SPAN | | | SHOULD CORRELATE WITH THE HEIGHT, BUT THE DIMENSION IN | | | THE COLUMN "SHUTTER SPAN" IS THE SAME AS THE WIDTH, NOT | | | THE HEIGHT. REVISE THE INSTALLATION SCHEDULE | | | ACCORDINGLY. | | | | | | 3. THE COMMENTS FROM THE PREVIOUS TWO REVIEWS CANNOT BE | | | EVALUATED UNTIL THE SPAN AND SUBSTRATE ARE KNOWN. | | | | | | | | | | | | | | | | | | |
|