| 2021-06-18 07:13:46 | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC 2020 RESIDENTIAL 301: | | | | | | 1. THE INSTALLATION SCHEDULE DOES NOT STATE WHAT THE | | | SUBSTRATE IS - BLOCK, CONCRETE? IS THE SUBSTRATE THE | | | SAME TOP AND BOTTOM? | | | | | | 2. ELCO TAPCONS IS NOT ONE LISTED ON PAGES 10-11 OF THE | | | PRODUCT APPROVAL SUBMITTED. REVISE THE INSTALLATION | | | SCHEDULE TO STATE WHICH FASTENER IS PROPOSED, USING THE | | | EXACT LANGUAGE AS ON THE PRODUCT APPROVAL. | | | | | | 3. 1 1/2" EDGE DISTANCE IS PROPOSED, NOTE THAT THIS | | | DIMENSION IS NOT ON THE ANCHOR SCHEDULES PAGES 10-11. | | | 1.25 WILL BE USED UNLESS THE ANCHOR SCHEDULE IS | | | REVISED. | | | | | | | | | | | | |
|