| 2021-06-01 09:52:18 | 06/01/21 1ST GAS REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. THE PHYSICAL ADDRESS OF THE RESIDENCE MUST BE ON |
| | PLANS IN FULL, NUMBER, STREET, CITY, STATE, AND ZIP |
| | CODE PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 2. PLEASE HAVE A SIGNATURE ON THE ISOMETRIC DRAWING OF |
| | THE PERSON DESIGNING THE SYSTEM, NOT IN ACCORDANCE WITH |
| | FLORIDA ADMINISTRATIVE CODE 61G15-23.001, FLORIDA |
| | STATUTE 471 PER THE WPB AMENDMENTS TO THE FBC SEC. |
| | 107.1 GENERAL. |
| | |
| | 3. PLEASE PROVIDE MANUFACTURES SPECIFICATIONS FOR ALL |
| | GAS EQUIPMENT TO VERIFY COMPLIANCE WITH 2020 FBC RES. |
| | SEC. G2408.1. |
| | |
| | 4. THIS TANK-LESS UNIT MAY CALL FOR A 10.5" WATER |
| | COLUMN, AND THE SERVICE METER DISCHARGES IS A 12" WATER |
| | COLUMN REQUIRING A REGULATOR FOR THIS UNIT AS PER THE |
| | MANUFACTURER'S SPECIFICATION. SUBMIT MANUFACTURERES |
| | SPECIFICATIONS FOR THE PRESSURE REGULATORS. REGULATORS |
| | INSTALLED ON THE EXTERIOR OF THE BUILDING SHALL BE |
| | APPROVED FOR OUTDOOR INSTALLATION PER THE 2020 FBC RES. |
| | SEC. G2421.1. |
| | |
| | 5. SUBMIT MANUFACTURERES SPECIFICATIONS FOR THE |
| | PRESSURE REGULATORS. REGULATORS INSTALLED ON THE |
| | EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR |
| | INSTALLATION PER THE 2020 FBC RES. SEC. G2421.1. |
| | |
| | 6. LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL |
| | BTU LOAD ON THE SYSTEM. REFER TO THE 2020 FBC RES. SEC. |
| | G2413. |
| | |
| | 7. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2020 |
| | FBC RES. SEC. G2407.1 AND G2439.4 (CLOTHES DRYERS). |
| | |
| | 8. SUPPOSE LOUVERS ARE BEING INSTALLED FOR THE |
| | COMBUSTION AIR AND SHOW LOCATION. THE LOUVERS CANNOT BE |
| | LOCATED ON AN EXTERIOR WALL THAT IS FIRE RATED AS THE |
| | FIRE RATING OF THE WALL MUST BE MAINTAINED PER THE WPB |
| | AMENDMENTS TO FBC SEC.107.2.1. |
| | |
| | 9. PLEASE SUBMIT A HOUSE PLAN SHOWING THE LOCATION OF |
| | THE TANK-LESS WATER HEATER AND THE LOCATION AND |
| | DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN RELATION |
| | TO THE WATER HEATER. THE LOCATION OF THE WATER HEATER |
| | SHALL COMPLY WITH THE MANUFACTURER'S INSTALLATION |
| | INSTRUCTIONS. THE HOUSE PLAN CAN BE HAND-DRAWN PER THE |
| | WPB AMENDMENTS TO THE FBC SEC. 107.2.1. INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | 10. ALL GAS APPLIANCES SHALL BE LISTED AND LABELED. THE |
| | INSTALLATION MANUALS FOR ALL GAS APPLIANCES/EQUIPMENT |
| | SHALL BE ONSITE AT THE INSPECTION TIME PER THE 2020 FBC |
| | RES. SEC. G2413.2 AND G2404.3. |
| | PLEASE SHOW AND LABEL ALL UNIONS IN FRONT OF REGULATOR |
| | 1" OF EITHER SIDE PER THE 2020 FBC RES. SEC G2421.2. |
| | |
| | 11. SHOW AND LABEL DRIP LEG ON EQUIPMENT INSTALLED, |
| | EXCEPT FOR APPLIANCES, RANGE, DRYERS & OD GRILLS PER |
| | THE 2020 FBC RES. SEC. G2419.2. |
| | |
| | 12. IF PIPES NOT IN CONDITION, SPACE NEEDS TO BE |
| | INSULATED WITH A MINIMUM R-3 PER THE 2020 FBC SEC. RE |
| | 403.5.3. PUT A NOTE ON PLANS. |
| | |
| | 13. SOME TANK-LESS UNITS REQUIRED CONDENSATE, AND THEY |
| | NEED TO BE 1' AWAY FROM THE STRUCTURE PER THE 2020 FBC |
| | SEC. R318.5. PUT A NOTE ON PLANS. |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION, |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| | |
| | LUIS A. CRESPO |
| | PLUMBING PLAN EXAMINER / INSPECTOR |
| | EMAIL: [email protected] OFFICE: 561 805-6720 |
| | |
| | |