| 2021-05-18 07:32:21 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | BUILDINGS WITH MORE THAN ONE CIRCUIT NEED A PANEL | | | INSTALLED AND A GROUNDING ELECRODE SYSTEM, 225.30, | | | 250.32 | | | | | | 250.32 BUILDINGS OR STRUCTURES SUPPLIED BY A FEEDER(S) | | | OR BRANCH CIRCUIT(S). (A) GROUNDING ELECTRODE. | | | BUILDING(S) OR STRUCTURE(S) SUPPLIED BY FEEDER(S) OR | | | BRANCH CIRCUIT(S) SHALL HAVE A GROUNDING ELECTRODE OR | | | GROUNDING ELECTRODE SYSTEM INSTALLED IN ACCORDANCE WITH | | | PART III OF ARTICLE 250. THE GROUNDING ELECTRODE | | | CONDUCTOR(S) SHALL BE CONNECTED IN ACCORDANCE WITH | | | 250.32(B) OR (C). WHERE THERE IS NO EXISTING GROUNDING | | | ELECTRODE, THE GROUNDING ELECTRODE(S) REQUIRED IN | | | 250.50 SHALL BE INSTALLED. | | | | | | 225.30 NUMBER OF SUPPLIES. A BUILDING OR OTHER | | | STRUCTURE THAT IS SERVED BY A BRANCH CIRCUIT OR FEEDER | | | ON THE LOAD SIDE OF A SERVICE DISCONNECTING MEANS SHALL | | | BE SUPPLIED BY ONLY ONE FEEDER OR BRANCH CIRCUIT UNLESS | | | PERMITTED IN 225.30(A) THROUGH (E). FOR THE PURPOSE OF | | | THIS SECTION, A MULTIWIRE BRANCH CIRCUIT SHALL BE | | | CONSIDERED A SINGLE CIRCUIT. | | | | | | PLEASE SUBMIT A RISER DIAGRM SHOWING THE LOCATION OF | | | THE SERVICE. 215.5 |
|