| 2021-05-04 12:42:08 | 05/04/21 1ST GAS REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. THE ADDRESS FOR THIS STRUCTURE HAS NO CHANGE OF |
| | OCCUPANCY IN THE CITY RECORDS AND NO BUILDING PERMIT ON |
| | FILE. ANY OWNER OR AGENT AUTHORIZED IN ACCORDANCE WITH |
| | FLORIDA STATUTE 489 WHO INTENDS TO CONSTRUCT, ENLARGE, |
| | ALTER, REPAIR, MOVE, DEMOLISH, OR CHANGE THE OCCUPANCY |
| | OF A BUILDING OR STRUCTURE, OR TO ERECT, INSTALL, |
| | ENLARGE, ALTER, REPAIR, REMOVE, CONVERT OR REPLACE ANY |
| | IMPACT-RESISTANT COVERINGS, ELECTRICAL, GAS, |
| | MECHANICAL, PLUMBING OR FIRE PROTECTION SYSTEM, OR |
| | ACCESSIBLE OR FLOOD-RESISTANT SITE ELEMENT, THE |
| | INSTALLATION OF WHICH IS REGULATED BY THIS CODE, OR TO |
| | CAUSE ANY SUCH WORK TO BE DONE, SHALL FIRST MAKE |
| | APPLICATION TO THE BUILDING OFFICIAL AND OBTAIN THE |
| | REQUIRED PERMIT PER THE WPB AMENDMENTS TO THE FBC SEC. |
| | 105.1. |
| | |
| | 2. PLEASE PROVIDE A DESCRIPTIVE SCOPE OF WORK THAT WILL |
| | BE PERFORMED ON THE PLANS, LIST FIXTURE APPURTENANCES |
| | BEING INSTALLED, AND THE EXTENT OF WORK YOU ARE DOING |
| | PER THE WPB AMENDMENTS TO THE FBC SEC. 101.2 SCOPE. |
| | |
| | 3. THE CLAIMED VALUE APPEARS TO BE UNDERESTIMATED ON |
| | THE APPLICATION. PLEASE PROVIDE A BONA FIDE SIGNED |
| | CONTRACT PER THE WPB AMENDMENTS TO THE FBC SEC. 109.3 |
| | BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF THE |
| | BUILDING OFFICIAL, THE CLAIMED VALUATION OF THE |
| | BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS, |
| | MECHANICAL, OR PLUMBING SYSTEMS APPEARS TO BE |
| | UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE |
| | DENIED UNLESS THE APPLICANT CAN SHOW DETAILED, QUANTITY |
| | ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS (EXCLUDING |
| | LAND VALUE) TO MEET THE APPROVAL OF THE BUILDING |
| | OFFICIAL. FOR PERMITTING PURPOSES, THE VALUATION OF |
| | BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT VALUE |
| | TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING, MECHANICAL, |
| | INTERIOR FINISH, RELATIVE SITE WORK, ARCHITECTURAL AND |
| | DESIGN FEES, MARKETING COSTS, OVERHEAD, AND PROFIT, |
| | EXCLUDING ONLY LAND VALUE. VALUATION REFERENCES MAY |
| | INCLUDE THE LATEST PUBLISHED DATA OF NATIONAL |
| | CONSTRUCTION COST ANALYSIS SERVICES (MARSHALL-SWIFT, |
| | MEANS, ETC.), AS PUBLISHED BY INTERNATIONAL CODE |
| | CONGRESS. THE BUILDING OFFICIAL SHALL SET THE FINAL |
| | BUILDING PERMIT VALUATION. |
| | |
| | 4. PLEASE PROVIDE A GAS RISER DIAGRAM REQUIRED PER THE |
| | WPB AMENDMENTS TO THE FBC SEC. 107.5.1.5 (9) COMMERCIAL |
| | GAS. |
| | |
| | 5. PLEASE SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY |
| | SHOWS THE LENGTH OF ALL CUT SECTIONS OF PIPE PER 2020 |
| | FBC FG SECS. 402.4.1, 402.4.2. |
| | |
| | 6. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL |
| | PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE |
| | CORRUGATED STAINLESS-STEEL TUBING (IF APPLICABLE) FOR |
| | EACH PIPE SIZE PER THE WPB AMENDMENTS FBC SEC.107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 7. TYPE OF GAS (LP OR NATURAL) PER THE WPB AMENDMENTS |
| | TO THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. |
| | |
| | 8. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM |
| | ON THE PLAN PER THE 2020 FBC FG SEC. 402.2. |
| | |
| | 9. SUBMIT MANUFACTURER'S SPECIFICATION |
| | SHEETS/INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO |
| | VERIFY COMPLIANCE WITH 2020 FBC FG SEC.305.1. |
| | |
| | 10. GAS APPLIANCES SHALL BE LISTED AND LABELED. THE |
| | INSTALLATION MANUALS FOR ALL GAS APPLIANCES/EQUIPMENT |
| | SHALL BE ONSITE AT THE TIME OF INSPECTION PER THE 2020 |
| | FBC FG SECS. 402.2 AND 301.3. |
| | |
| | 11. LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL |
| | BTU LOAD ON THE SYSTEM. REFER TO THE 2020 FBC FG SECS. |
| | 401.8 THROUGH 402.6.1 AND TABLES 402.4 (1) THROUGH |
| | 402.4 (37). |
| | |
| | 12. SHOW THE DISTANCE FROM THE POINT OF DELIVERY (GAS |
| | METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER THE 2020 FBC |
| | FG SEC. 402.4.1. |
| | |
| | 13. PLEASE SUBMIT THE SIZING TABLE USED IN THE DESIGN |
| | FOR THE GAS SYSTEM OR PLACE A NOTE ON BOTH SETS OF |
| | PLANS LISTING THE SIZING TABLES FROM GAS CODES OR |
| | ANOTHER STANDARD THAT WERE USED IN THE DESIGN OF THIS |
| | SYSTEM PER THE 2020 FBC FG SEC. 402.3. |
| | |
| | 14. THE PHYSICAL ADDRESS OF THE PROJECT MUST BE ON |
| | PLANS IN FULL, NUMBER, STREET, CITY, STATE, AND ZIP |
| | CODE PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 15. IF APPLICABLE, PLEASE SUBMIT THE MANUFACTURER'S |
| | SPECIFICATIONS FOR THE PRESSURE REGULATORS. REGULATORS |
| | INSTALLED ON THE EXTERIOR OF THE BUILDING SHALL BE |
| | APPROVED FOR OUTDOOR INSTALLATION PER THE 2020 FBC FG |
| | SEC. 410.1. |
| | |
| | 16. PLEASE SHOW ALL UNIONS IN FRONT OF REGULATOR 1' OF |
| | EITHER SIDE PER THE 2020 FBC FG SEC 410.2. |
| | |
| | 17. SHOW DRIP LEG ON EQUIPMENT INSTALLED, EXCEPT FOR |
| | APPLIANCES, RANGE, DRYERS & OD GRILLS PER THE 2020 FBC |
| | FG 408.2. |
| | |
| | 18. PLEASE PROVIDE THE SIGNATURE OF ALL INFORMATION, |
| | DRAWINGS, SPECIFICATIONS, AND ACCOMPANYING DATA THAT |
| | SHALL BEAR THE PRINTED NAME AND SIGNATURE OF THE PERSON |
| | RESPONSIBLE FOR THE DESIGN PER THE WPB AMENDMENTS TO |
| | THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| | |
| | LUIS A. CRESPO |
| | PLUMBING PLAN EXAMINER / INSPECTOR |
| | EMAIL: [email protected] OFFICE: 561 805-6720 |
| | |