| Plan Review Notes For Permit 21041405 |
| Permit Number |
21041405 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2021-08-20 16:18:55 | 1) THE OUTDOOR AIR CALCULATIONS HAVE THE SPACE TYPE | | | LISTED ON ALL ROOMS AS OFFICE SPACES THIS IS INCORRECT. | | | PLEASE PROVIDE THE OUTDOOR AIR CALCULATIONS BASED ON | | | USE OF SPACE FOR THE ENTIRE TENANT SPACE. FBC M | | | 403.3.1.1 AND TABLE 403.3.1.1 | | | | | | 2) PLEASE SHOW THE REQUIRED VENTILATION FOR THE SOILED | | | STORAGE ROOM 1012 | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|