2021-07-27 15:13:382ND REVIEW FBC-2020 PLUMBING
 PERMIT-21041405
 7/27/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE
 1ST REVIEW ARE LISTED BELOW WITH ADDITIONAL NOTES IN
 CAPS.
  
 1) FAILED. PROVIDE SANITARY DRAINAGE AND VENT, AND
 WATER DISTRIBUTION ISOMETRIC DRAWINGS- SECTIONS
 107.3.5.1.3 AND 107.2.1 WPB. SHOW LOICATIONS OF
 REQUIRED SHUTOFF VALVES AT THE BASE OF THE RISER PIPE
 AND AT THE TOP OF DOWN FEEDING PIPE- SECTION 606.1 FBC
 P.
  
 2) FAILED. REFER TO TABLE 403.1 AND PROVIDE PLUMBING
 FIXTURE CALCULATIONS. PROVIDE A SCHEDULE THAT INDICATES
 THE REQUIRED AND PROVIDED NUMBER OF PLUMBING FIXTURES
 BASED ON THE OCCUPANCY CLASSIFICATION OF THE SPACE AND
 OCCUPANT LOAD. SHOW THE CALCULATIONS FOR BOTH PUBLIC
 AND EMPLOYEE USE IN ACCORDANCE WITH SECTION 403.3 FBC P
 AND SHOW THAT THE MINIMUM FIXTURES HAVE BEEN PROVIDED
 FOR EACH. PLEASE LABEL TLT 1004 AS EITHER STAFF OR
 PATIENT ON THE ARCHITECTURAL AND PLUMBING PLANS.
 BECAUSE THE PLANS ARE INDICATING SEPARATE FACILITIES
 FOR PUBLIC AND STAFF USE, THEN AN EQUAL NUMBER OF WATER
 CLOSETS AND LAVATORIES FOR MALE AND FEMALE USE SHALL BE
 PROVIDED TO BOTH THE PUBLIC AND THE STAFF. PLEASE
 REVISE THE CALCULATION SCHEDULE ON G1.01 TO LIST THE
 REQUIRED AND PROVIDED NUMBER OF MALE AND FEMALE
 FIXTURES FOR BOTH THE PUBLIC AND STAFF, AND IDENTIFY
 THE LOCATIONS ON THE PLANS.
  
 8) FAILED. P101 & P201: PLASTER TRAPS ARE SPECIFIED.
 PLEASE ADD THE MAKE AND MODEL OF THE TRAPS TO THE
 FIXTURE SCHEDULE ON P001. A) PROVIDE AN ENLARGED
 PLUMBING PIPING INSTALLATION DETAIL- SECTION 1003.2 FBC
 P. B) PROVIDE A NARRATIVE TO CLARIFY WHAT PROCESSES ARE
 BEING CONDUCTED IN THE FACILITY THAT WILL REQUIRE
 INSTALLATION OF THE TRAPS- SECTION 107.2.1 WPB. DETAIL
 AND NARRATIVE NOT PROVIDED.
  
 9) FAILED. PLEASE INDICATE THE TYPE OF WALL FINISH
 MATERIAL TO BE INSTALLED AROUND THE NEW SECOND FLOOR
 MOP SINK- SEE SECTION 310.3 FBC P AND SECTION 1210.2.2
 FBC B. THE RESPONSE INDICATES "RIGID SHEET WALL
 SURROUND". PLEASE IDENTIFY WHAT THE SHEET WALL
 MATERIALS ARE.
  
 13) FAILED D, F, G. A201 MISSING ACCESSIBILITY DETAILS
 FOR THE TOILET ROOMS PER FBC ACC: PLEASE NOTE THAT ALL
 FIGUIRES IN THE TYPICAL DETAILS ON G401 SHALL BE IN
 COMPLIANCE WITH THE FLORIDA BUILDING CODE- ACCESIBILITY
 7TH EDITION 2020.
  
 D) FAILED. LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF
 GRAB BARS FOR THE WATER CLOSETS- SECTION 604.5 & 609.4,
 FIGURES 604. SHEET G401: VERTICAL GRAB BAR IS SHOWN IN
 THE TYP. ACCESSIBLE TOILET ELEVATIONS. GRAB BARS SHALL
 BE INSTALLED IN HORIZONTAL POSITIONS.
  
 F) FAILED. CENTERLINES OF THE TOILET PAPER DISPENSER
 MEASURED FROM THE FRONTS OF THE WATER CLOSETS- SECTION
 AND FIGURE 604.7. THE CENTERLINE SHOWN IN THE TYP.
 ELEVATION IS NOT IN THE CENTER OF THE DISPENSER- PLEASE
 CORRECT.
  
 G) FAILED. KNEE AND TOE CLEARANCES FOR THE LAVATORIES-
 SECTION 606.2. NOT PROVIDED.
  
 14) FAILED. A101, A102, A801: INDICATE THE CLEAR FLOOR
 SPACE DIAGRAMS AND DIMENSIONS FOR THE ACCESSIBLE SINKS
 ON THE PLAN. SHOW EITHER A FORWARD OR PARALLEL APPROACH
 WHERE REQUIRED- SEE SECTIONS 212.3 & 606.2 FBC ACC. NOT
 PROVIDED. THE ARCHITECT'S RESPONSE REFERENCES P2
 LAVATORY SINKS. LOCATIONS AND DETAILS FOR THE OTHER
 ACCESSIBLE SINKS IN THE LOUNGES, EAXAM AND TREATMENT
 ROOMS ETC.NOT COMPLETELY PROVIDED.
  
 16) FAILED. A102 & A801: PROVIDE THE CLEAR FLOOR SPACE
 DIAGRAM AND DIMENSION FOR THE WATER COOLER IN ROOM
 2028. A) ADD THE COOLER TO THE FIXTURE SCHEDULE ON
 P001. B) SUBMIT MANUFACTURER'S SPECIFICATIONS AND
 PROVIDE AN ELEVATION DRAWING TO SHOW COMPLIANCE WITH
 SECTIONS 308 & 309 FBC ACC- REACH RANGES AND CONTROLS.
 THE REQUESTED PRODUCT SPECS WERE NOT PROVIDED.
  
 17) FAILED. P001: PROVIDE HOT WATER PIPE INSULATION
 SPECIFICATIONS IN ACCORDANCE WITH TABLE C403.2.10 FBC
 EC. NOT PROVIDED. THE ARCHITECT REFERENCES THE PROJECT
 SPECIFICATION BOOK WHICH WAS NOT SUBMITTED AND WHICH
 WILL NOT BE REVIEWED.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  