| 2021-07-27 15:13:38 | 2ND REVIEW FBC-2020 PLUMBING |
| | PERMIT-21041405 |
| | 7/27/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE |
| | 1ST REVIEW ARE LISTED BELOW WITH ADDITIONAL NOTES IN |
| | CAPS. |
| | |
| | 1) FAILED. PROVIDE SANITARY DRAINAGE AND VENT, AND |
| | WATER DISTRIBUTION ISOMETRIC DRAWINGS- SECTIONS |
| | 107.3.5.1.3 AND 107.2.1 WPB. SHOW LOICATIONS OF |
| | REQUIRED SHUTOFF VALVES AT THE BASE OF THE RISER PIPE |
| | AND AT THE TOP OF DOWN FEEDING PIPE- SECTION 606.1 FBC |
| | P. |
| | |
| | 2) FAILED. REFER TO TABLE 403.1 AND PROVIDE PLUMBING |
| | FIXTURE CALCULATIONS. PROVIDE A SCHEDULE THAT INDICATES |
| | THE REQUIRED AND PROVIDED NUMBER OF PLUMBING FIXTURES |
| | BASED ON THE OCCUPANCY CLASSIFICATION OF THE SPACE AND |
| | OCCUPANT LOAD. SHOW THE CALCULATIONS FOR BOTH PUBLIC |
| | AND EMPLOYEE USE IN ACCORDANCE WITH SECTION 403.3 FBC P |
| | AND SHOW THAT THE MINIMUM FIXTURES HAVE BEEN PROVIDED |
| | FOR EACH. PLEASE LABEL TLT 1004 AS EITHER STAFF OR |
| | PATIENT ON THE ARCHITECTURAL AND PLUMBING PLANS. |
| | BECAUSE THE PLANS ARE INDICATING SEPARATE FACILITIES |
| | FOR PUBLIC AND STAFF USE, THEN AN EQUAL NUMBER OF WATER |
| | CLOSETS AND LAVATORIES FOR MALE AND FEMALE USE SHALL BE |
| | PROVIDED TO BOTH THE PUBLIC AND THE STAFF. PLEASE |
| | REVISE THE CALCULATION SCHEDULE ON G1.01 TO LIST THE |
| | REQUIRED AND PROVIDED NUMBER OF MALE AND FEMALE |
| | FIXTURES FOR BOTH THE PUBLIC AND STAFF, AND IDENTIFY |
| | THE LOCATIONS ON THE PLANS. |
| | |
| | 8) FAILED. P101 & P201: PLASTER TRAPS ARE SPECIFIED. |
| | PLEASE ADD THE MAKE AND MODEL OF THE TRAPS TO THE |
| | FIXTURE SCHEDULE ON P001. A) PROVIDE AN ENLARGED |
| | PLUMBING PIPING INSTALLATION DETAIL- SECTION 1003.2 FBC |
| | P. B) PROVIDE A NARRATIVE TO CLARIFY WHAT PROCESSES ARE |
| | BEING CONDUCTED IN THE FACILITY THAT WILL REQUIRE |
| | INSTALLATION OF THE TRAPS- SECTION 107.2.1 WPB. DETAIL |
| | AND NARRATIVE NOT PROVIDED. |
| | |
| | 9) FAILED. PLEASE INDICATE THE TYPE OF WALL FINISH |
| | MATERIAL TO BE INSTALLED AROUND THE NEW SECOND FLOOR |
| | MOP SINK- SEE SECTION 310.3 FBC P AND SECTION 1210.2.2 |
| | FBC B. THE RESPONSE INDICATES "RIGID SHEET WALL |
| | SURROUND". PLEASE IDENTIFY WHAT THE SHEET WALL |
| | MATERIALS ARE. |
| | |
| | 13) FAILED D, F, G. A201 MISSING ACCESSIBILITY DETAILS |
| | FOR THE TOILET ROOMS PER FBC ACC: PLEASE NOTE THAT ALL |
| | FIGUIRES IN THE TYPICAL DETAILS ON G401 SHALL BE IN |
| | COMPLIANCE WITH THE FLORIDA BUILDING CODE- ACCESIBILITY |
| | 7TH EDITION 2020. |
| | |
| | D) FAILED. LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF |
| | GRAB BARS FOR THE WATER CLOSETS- SECTION 604.5 & 609.4, |
| | FIGURES 604. SHEET G401: VERTICAL GRAB BAR IS SHOWN IN |
| | THE TYP. ACCESSIBLE TOILET ELEVATIONS. GRAB BARS SHALL |
| | BE INSTALLED IN HORIZONTAL POSITIONS. |
| | |
| | F) FAILED. CENTERLINES OF THE TOILET PAPER DISPENSER |
| | MEASURED FROM THE FRONTS OF THE WATER CLOSETS- SECTION |
| | AND FIGURE 604.7. THE CENTERLINE SHOWN IN THE TYP. |
| | ELEVATION IS NOT IN THE CENTER OF THE DISPENSER- PLEASE |
| | CORRECT. |
| | |
| | G) FAILED. KNEE AND TOE CLEARANCES FOR THE LAVATORIES- |
| | SECTION 606.2. NOT PROVIDED. |
| | |
| | 14) FAILED. A101, A102, A801: INDICATE THE CLEAR FLOOR |
| | SPACE DIAGRAMS AND DIMENSIONS FOR THE ACCESSIBLE SINKS |
| | ON THE PLAN. SHOW EITHER A FORWARD OR PARALLEL APPROACH |
| | WHERE REQUIRED- SEE SECTIONS 212.3 & 606.2 FBC ACC. NOT |
| | PROVIDED. THE ARCHITECT'S RESPONSE REFERENCES P2 |
| | LAVATORY SINKS. LOCATIONS AND DETAILS FOR THE OTHER |
| | ACCESSIBLE SINKS IN THE LOUNGES, EAXAM AND TREATMENT |
| | ROOMS ETC.NOT COMPLETELY PROVIDED. |
| | |
| | 16) FAILED. A102 & A801: PROVIDE THE CLEAR FLOOR SPACE |
| | DIAGRAM AND DIMENSION FOR THE WATER COOLER IN ROOM |
| | 2028. A) ADD THE COOLER TO THE FIXTURE SCHEDULE ON |
| | P001. B) SUBMIT MANUFACTURER'S SPECIFICATIONS AND |
| | PROVIDE AN ELEVATION DRAWING TO SHOW COMPLIANCE WITH |
| | SECTIONS 308 & 309 FBC ACC- REACH RANGES AND CONTROLS. |
| | THE REQUESTED PRODUCT SPECS WERE NOT PROVIDED. |
| | |
| | 17) FAILED. P001: PROVIDE HOT WATER PIPE INSULATION |
| | SPECIFICATIONS IN ACCORDANCE WITH TABLE C403.2.10 FBC |
| | EC. NOT PROVIDED. THE ARCHITECT REFERENCES THE PROJECT |
| | SPECIFICATION BOOK WHICH WAS NOT SUBMITTED AND WHICH |
| | WILL NOT BE REVIEWED. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |