| 2021-06-16 18:36:19 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT-21041405 |
| | 6/16/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PROVIDE SANITARY DRAINAGE AND VENT, AND WATER |
| | DISTRIBUTION ISOMETRIC DRAWINGS- SECTIONS 107.3.5.1.3 |
| | AND 107.2.1 WPB. |
| | |
| | 2) REFER TO TABLE 403.1 AND PROVIDE PLUMBING FIXTURE |
| | CALCULATIONS. PROVIDE A SCHEDULE THAT INDICATES THE |
| | REQUIRED AND PROVIDED NUMBER OF PLUMBING FIXTURES BASED |
| | ON THE OCCUPANCY CLASSIFICATION OF THE SPACE AND |
| | OCCUPANT LOAD. SHOW THE CALCULATIONS FOR BOTH PUBLIC |
| | AND EMPLOYEE USE IN ACCORDANCE WITH SECTION 403.3 FBC P |
| | AND SHOW THAT THE MINIMUM FIXTURES HAVE BEEN PROVIDED |
| | FOR EACH. PLEASE LABEL TLT 1004 AS EITHER STAFF OR |
| | PATIENT ON THE ARCHITECTURAL AND PLUMBING PLANS. |
| | |
| | 3) SHEET P201: PLEASE PROVIDE A NOTE BY EACH CIRCULAR |
| | SYMBOL SHOWN ON THE PLAN I.E. KEYNOTE 4 IS SPECIFYING A |
| | FLOOR DRAIN AND 5 IS SPECIFYING A PLASTER TRAP. |
| | |
| | 4) P001: PROVIDE THE EFFICIENCY RATINGS OF THE WATER |
| | HEATERS IN THE SCHEDULE- TABLE C404.2 FBC EC. |
| | |
| | 5) P001: PROVIDE PANS AND PAN DRAINS FOR THE WATER |
| | HEATERS- SECTION 504.7 FBC P. |
| | |
| | 6) P201: NEW FIXTURE DRAIN INSTALLATIONS MAY REQUIRE |
| | THE FLOOR TO BE X-RAYED TO IN ORDER TO LOCATE |
| | REINFORCING STEEL OR POST STRESSED FLOOR TENDONS. |
| | PLEASE PLACE A NOTE ON THE PLANS TO VERIFY COMPLIANCE |
| | WILL BE MET- SECTION 107.2.1 WPB. |
| | |
| | 7) P201: NEW FIXTURE DRAIN PIPE PENETRATIONS OF THE |
| | EXISTING SLAB WILL REQUIRE FIRESTOPPING TO SEAL THE |
| | ANNULAR SPACE AROUND THE PIPING. PROVIDE A UL TESTED |
| | AND APPROVED FIRESTOPPING ASSEMBLY DETAIL ON THE PLAN- |
| | SECTION 315.1 FBC P AND SECTION 714.4.1.2 FBC B. |
| | |
| | 8) P101 & P201: PLASTER TRAPS ARE SPECIFIED. PLEASE ADD |
| | THE MAKE AND MODEL OF THE TRAPS TO THE FIXTURE SCHEDULE |
| | ON P001. A) PROVIDE AN ENLARGED PLUMBING PIPING |
| | INSTALLATION DETAIL- SECTION 1003.2 FBC P. B) PROVIDE A |
| | NARRATIVE TO CLARIFY WHAT PROCESSES ARE BEING CONDUCTED |
| | IN THE FACILITY THAT WILL REQUIRE INSTALLATION OF THE |
| | TRAPS- SECTION 107.2.1 WPB. |
| | |
| | 9) PLEASE INDICATE THE TYPE OF WALL FINISH MATERIAL TO |
| | BE INSTALLED AROUND THE NEW SECOND FLOOR MOP SINK- SEE |
| | SECTION 310.3 FBC P AND SECTION 1210.2.2 FBC B. |
| | |
| | 10) SHEET A201: DOORS SHALL NOT SWING INTO THE CLEAR |
| | FLOOR SPACE OF THE LAVATORIES- SECTION 603.2.3 FBC ACC. |
| | |
| | 11) A201: PROVIDE THE DIMENSIONS OF THE CLEAR FLOOR |
| | SPACES FOR THE WATER CLOSETS AND LAVATORIES- SECTIONS |
| | 604.3 & 606.2 FBC ACC. |
| | |
| | 12) A201: PROVIDE THE TURNING SPACE DIAMETERS- SECTION |
| | 304.3. FBC ACC. |
| | |
| | 13) A201 MISSING ACCESSIBILITY DETAILS FOR THE TOILET |
| | ROOMS PER FBC ACC: |
| | |
| | A) HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED |
| | FLOORS- SECTION 604.4. |
| | |
| | B) HEIGHTS OF THE LAVATORY SINK RIM OR COUNTER SURFACE |
| | FROM THE FINISHED FLOOR- SECTION 606.3. |
| | |
| | C) HEIGHTS OF THE MIRRORS FROM THE FINISHED FLOORS TO |
| | THE REFLECTIVE SURFACES- SECTION 603.3. |
| | |
| | D) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB |
| | BARS FOR THE WATER CLOSETS- SECTION 604.5 & 609.4, |
| | FIGURES 604. |
| | |
| | E) LOCATION OF THE WATER CLOSET FLUSH CONTROLS - |
| | SECTION 604.6. |
| | |
| | F) CENTERLINES OF THE TOILET PAPER DISPENSER MEASURED |
| | FROM THE FRONTS OF THE WATER CLOSETS- SECTION AND |
| | FIGURE 604.7. |
| | |
| | G) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SECTION |
| | 606.2. |
| | |
| | 14) A101, A102, A801: INDICATE THE CLEAR FLOOR SPACE |
| | DIAGRAMS AND DIMENSIONS FOR THE ACCESSIBLE SINKS ON THE |
| | PLAN. SHOW EITHER A FORWARD OR PARALLEL APPROACH WHERE |
| | REQUIRED- SEE SECTIONS 212.3 & 606.2 FBC ACC. |
| | |
| | 15) PLEASE REFER TO COMMENT # 2 CONCERNING DRINKING |
| | FOUNTAINS. IN ACCORDANCE WITH TABLE 403.1 DRINKING |
| | FOUNTAINS ARE REQUIRED FIXTURES. PLEASE SHOW THE |
| | LOCATIONS OF THE REQUIRED DRINKING FOUNTAINS AND |
| | PROVIDE DRINKING FOUNTAIN INSTALLATION DETAILS AND |
| | ELEVATION VIEWS SHOWING KNEE AND TOE CLEARANCES, SPOUT |
| | HEIGHTS, AND SPOUT LOCATIONS- SECTIONS 306, 307, AND |
| | 602 FBC ACC. SHOW THE REQUIRED 30 X 48 IN. CLEAR FLOOR |
| | SPACE FOR A FORWARD WHEELCHAIR APPROACH TO THE |
| | FOUNTAIN- SECTION 602.2 FBC ACC, AND SHOW HOW THE |
| | LOCATIONS OF THE FOUNTAINS WILL BE IN COMPLIANCE WITH |
| | SECTION 307.2 PROTRUSION LIMITS. |
| | |
| | 16) A102 & A801: PROVIDE THE CLEAR FLOOR SPACE DIAGRAM |
| | AND DIMENSION FOR THE WATER COOLER IN ROOM 2028. A) ADD |
| | THE COOLER TO THE FIXTURE SCHEDULE ON P001. B) SUBMIT |
| | MANUFACTURER?S SPECIFICATIONS AND PROVIDE AN ELEVATION |
| | DRAWING TO SHOW COMPLIANCE WITH SECTIONS 308 & 309 FBC |
| | ACC- REACH RANGES AND CONTROLS. |
| | |
| | 17) P001: PROVIDE HOT WATER PIPE INSULATION |
| | SPECIFICATIONS IN ACCORDANCE WITH TABLE C403.2.10 FBC |
| | EC. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |