Plan Review Notes
Plan Review Notes For Permit 21041405
Permit Number 21041405
Review Stop P
Sequence Number 1
Notes
Date Text
2021-06-16 18:36:191ST REVIEW FBC-2020 PLUMBING
 PERMIT-21041405
 6/16/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE SANITARY DRAINAGE AND VENT, AND WATER
 DISTRIBUTION ISOMETRIC DRAWINGS- SECTIONS 107.3.5.1.3
 AND 107.2.1 WPB.
  
 2) REFER TO TABLE 403.1 AND PROVIDE PLUMBING FIXTURE
 CALCULATIONS. PROVIDE A SCHEDULE THAT INDICATES THE
 REQUIRED AND PROVIDED NUMBER OF PLUMBING FIXTURES BASED
 ON THE OCCUPANCY CLASSIFICATION OF THE SPACE AND
 OCCUPANT LOAD. SHOW THE CALCULATIONS FOR BOTH PUBLIC
 AND EMPLOYEE USE IN ACCORDANCE WITH SECTION 403.3 FBC P
 AND SHOW THAT THE MINIMUM FIXTURES HAVE BEEN PROVIDED
 FOR EACH. PLEASE LABEL TLT 1004 AS EITHER STAFF OR
 PATIENT ON THE ARCHITECTURAL AND PLUMBING PLANS.
  
 3) SHEET P201: PLEASE PROVIDE A NOTE BY EACH CIRCULAR
 SYMBOL SHOWN ON THE PLAN I.E. KEYNOTE 4 IS SPECIFYING A
 FLOOR DRAIN AND 5 IS SPECIFYING A PLASTER TRAP.
  
 4) P001: PROVIDE THE EFFICIENCY RATINGS OF THE WATER
 HEATERS IN THE SCHEDULE- TABLE C404.2 FBC EC.
  
 5) P001: PROVIDE PANS AND PAN DRAINS FOR THE WATER
 HEATERS- SECTION 504.7 FBC P.
  
 6) P201: NEW FIXTURE DRAIN INSTALLATIONS MAY REQUIRE
 THE FLOOR TO BE X-RAYED TO IN ORDER TO LOCATE
 REINFORCING STEEL OR POST STRESSED FLOOR TENDONS.
 PLEASE PLACE A NOTE ON THE PLANS TO VERIFY COMPLIANCE
 WILL BE MET- SECTION 107.2.1 WPB.
  
 7) P201: NEW FIXTURE DRAIN PIPE PENETRATIONS OF THE
 EXISTING SLAB WILL REQUIRE FIRESTOPPING TO SEAL THE
 ANNULAR SPACE AROUND THE PIPING. PROVIDE A UL TESTED
 AND APPROVED FIRESTOPPING ASSEMBLY DETAIL ON THE PLAN-
 SECTION 315.1 FBC P AND SECTION 714.4.1.2 FBC B.
  
 8) P101 & P201: PLASTER TRAPS ARE SPECIFIED. PLEASE ADD
 THE MAKE AND MODEL OF THE TRAPS TO THE FIXTURE SCHEDULE
 ON P001. A) PROVIDE AN ENLARGED PLUMBING PIPING
 INSTALLATION DETAIL- SECTION 1003.2 FBC P. B) PROVIDE A
 NARRATIVE TO CLARIFY WHAT PROCESSES ARE BEING CONDUCTED
 IN THE FACILITY THAT WILL REQUIRE INSTALLATION OF THE
 TRAPS- SECTION 107.2.1 WPB.
  
 9) PLEASE INDICATE THE TYPE OF WALL FINISH MATERIAL TO
 BE INSTALLED AROUND THE NEW SECOND FLOOR MOP SINK- SEE
 SECTION 310.3 FBC P AND SECTION 1210.2.2 FBC B.
  
 10) SHEET A201: DOORS SHALL NOT SWING INTO THE CLEAR
 FLOOR SPACE OF THE LAVATORIES- SECTION 603.2.3 FBC ACC.
  
 11) A201: PROVIDE THE DIMENSIONS OF THE CLEAR FLOOR
 SPACES FOR THE WATER CLOSETS AND LAVATORIES- SECTIONS
 604.3 & 606.2 FBC ACC.
  
 12) A201: PROVIDE THE TURNING SPACE DIAMETERS- SECTION
 304.3. FBC ACC.
  
 13) A201 MISSING ACCESSIBILITY DETAILS FOR THE TOILET
 ROOMS PER FBC ACC:
  
 A) HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED
 FLOORS- SECTION 604.4.
  
 B) HEIGHTS OF THE LAVATORY SINK RIM OR COUNTER SURFACE
 FROM THE FINISHED FLOOR- SECTION 606.3.
  
 C) HEIGHTS OF THE MIRRORS FROM THE FINISHED FLOORS TO
 THE REFLECTIVE SURFACES- SECTION 603.3.
  
 D) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS FOR THE WATER CLOSETS- SECTION 604.5 & 609.4,
 FIGURES 604.
  
 E) LOCATION OF THE WATER CLOSET FLUSH CONTROLS -
 SECTION 604.6.
  
 F) CENTERLINES OF THE TOILET PAPER DISPENSER MEASURED
 FROM THE FRONTS OF THE WATER CLOSETS- SECTION AND
 FIGURE 604.7.
  
 G) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SECTION
 606.2.
  
 14) A101, A102, A801: INDICATE THE CLEAR FLOOR SPACE
 DIAGRAMS AND DIMENSIONS FOR THE ACCESSIBLE SINKS ON THE
 PLAN. SHOW EITHER A FORWARD OR PARALLEL APPROACH WHERE
 REQUIRED- SEE SECTIONS 212.3 & 606.2 FBC ACC.
  
 15) PLEASE REFER TO COMMENT # 2 CONCERNING DRINKING
 FOUNTAINS. IN ACCORDANCE WITH TABLE 403.1 DRINKING
 FOUNTAINS ARE REQUIRED FIXTURES. PLEASE SHOW THE
 LOCATIONS OF THE REQUIRED DRINKING FOUNTAINS AND
 PROVIDE DRINKING FOUNTAIN INSTALLATION DETAILS AND
 ELEVATION VIEWS SHOWING KNEE AND TOE CLEARANCES, SPOUT
 HEIGHTS, AND SPOUT LOCATIONS- SECTIONS 306, 307, AND
 602 FBC ACC. SHOW THE REQUIRED 30 X 48 IN. CLEAR FLOOR
 SPACE FOR A FORWARD WHEELCHAIR APPROACH TO THE
 FOUNTAIN- SECTION 602.2 FBC ACC, AND SHOW HOW THE
 LOCATIONS OF THE FOUNTAINS WILL BE IN COMPLIANCE WITH
 SECTION 307.2 PROTRUSION LIMITS.
  
 16) A102 & A801: PROVIDE THE CLEAR FLOOR SPACE DIAGRAM
 AND DIMENSION FOR THE WATER COOLER IN ROOM 2028. A) ADD
 THE COOLER TO THE FIXTURE SCHEDULE ON P001. B) SUBMIT
 MANUFACTURER?S SPECIFICATIONS AND PROVIDE AN ELEVATION
 DRAWING TO SHOW COMPLIANCE WITH SECTIONS 308 & 309 FBC
 ACC- REACH RANGES AND CONTROLS.
  
 17) P001: PROVIDE HOT WATER PIPE INSULATION
 SPECIFICATIONS IN ACCORDANCE WITH TABLE C403.2.10 FBC
 EC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  