| 2021-06-10 22:15:14 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. PROVIDE LOAD CALCULATION OF SERVICE TO INCLUDE BOTH |
| | NEW AND EXISTING LOADS. NEC 220 FBC 107.2.1 |
| | |
| | 2. DESIGN PROFESSIONAL TO SPECIFY WHAT AREAS ARE |
| | "PATIENT CARE AREAS" AND WIRING METHOD. FBC 107.2.1 NEC |
| | 517 |
| | |
| | 3. NO CONDUIT OR WIRE SIZE SHOWN FOR NEW SERVICE ITEMS. |
| | FBC 107.2.1 |
| | |
| | 4. ALL FIRE ALARM SHOWN MUST BE REMOVED FROM PLAN AND |
| | APPLIED FOR UNDER A SEPARATE PERMIT WITH SEPARATE |
| | DRAWINGS. FBC 105.1 |
| | |
| | 5. PROVIDE NOTE ON PLANS THAT ALL LOW VOLTAGE SYSTEMS |
| | SHOWN ON PLANS WILL REQUIRE SEPARATE LOW VOLTAGE |
| | PERMITS, A NOTE ON PLAN WILL SUFFICE. FBC 107.2.1 |
| | |
| | |
| | |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | CODES IN EFFECT: |
| | |
| | HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B |
| | UILDING-PERMIT-FORMS |
| | |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2020 7TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| | 7TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |
| | FRANK GIAQUINTO III |
| | ELECTRICAL INSPECTOR |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | [email protected] |
| | CELL: 561-805-6744 |
| | |
| | |