Plan Review Notes
Plan Review Notes For Permit 21041405
Permit Number 21041405
Review Stop E
Sequence Number 1
Notes
Date Text
2021-06-10 22:15:14ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE LOAD CALCULATION OF SERVICE TO INCLUDE BOTH
 NEW AND EXISTING LOADS. NEC 220 FBC 107.2.1
  
 2. DESIGN PROFESSIONAL TO SPECIFY WHAT AREAS ARE
 "PATIENT CARE AREAS" AND WIRING METHOD. FBC 107.2.1 NEC
 517
  
 3. NO CONDUIT OR WIRE SIZE SHOWN FOR NEW SERVICE ITEMS.
 FBC 107.2.1
  
 4. ALL FIRE ALARM SHOWN MUST BE REMOVED FROM PLAN AND
 APPLIED FOR UNDER A SEPARATE PERMIT WITH SEPARATE
 DRAWINGS. FBC 105.1
  
 5. PROVIDE NOTE ON PLANS THAT ALL LOW VOLTAGE SYSTEMS
 SHOWN ON PLANS WILL REQUIRE SEPARATE LOW VOLTAGE
 PERMITS, A NOTE ON PLAN WILL SUFFICE. FBC 107.2.1
  
  
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-805-6744
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved