| 2021-05-26 17:31:28 | 1ST REVIEW FBC-2020 RES. |
| | PERMIT- 21041393 |
| | 5/26/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| | 2020 |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET E.01: GAS RISER DRAWINGS SHALL BE PREPARED BY |
| | EITHER A FL. LICENSED DESIGN PROFESSIONAL OR A FL. |
| | LICENSED PLUMBING OR GAS CONTRACTOR. THE ELECTRICAL |
| | CONTRACTOR IS NOT PERMITTED TO DESIGN THE SYSTEM AND |
| | PREPARE THE DRAWING- SECTION 107.2.1 WPB, AND FLORIDA |
| | STATUTES 471.003(2)(H) & 471.025. |
| | |
| | 2) 1) PROVIDE A COMPLETE GAS RISER DRAWING THAT |
| | INCLUDES ALL NEW AND EXISTING GAS PIPING AND APPLIANCES |
| | AT THE RESIDENCE- SECTION G2412.3 & G2412.4 FBC RES. |
| | CITY OF WPB BUILDING DEPT. RECORDS INDICATES A GAS POOL |
| | HEATER WAS INSTALLED UNDER PERMIT- 02011630. REFER TO |
| | FBC RES. CHAPTER 24 FUEL GAS- THE RISER SHALL INDICATE: |
| | |
| | A) TOTAL BTU LOAD AND INDIVIDUAL APPLIANCE BTU LOADS. |
| | B) TYPES AND SIZES OF PIPING. |
| | C) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER |
| | TO THE MOST REMOTE APPLIANCE OUTLET. |
| | D) BRANCH AND CUT PIPE LENGTH MEASUREMENTS. |
| | E) LOCATIONS OF REGULATORS, SHUTOFF VALVES, AND PIPE |
| | UNIONS. |
| | F) OUTLET PRESSURES AT REGULATORS. |
| | G) LOCATIONS AND TYPES OF PIPE SLEEVES. |
| | H) PIPE SIZING TABLES. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |