| 2021-05-13 13:25:16 | 05/13/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | |
| | 1. ON SHEET A-0.0, UNDER SUBMITTAL NOTES ITEM #1, THE |
| | CODE REFERENCE USED REFERS TO THE 2017 6TH EDITION. |
| | PLEASE CORRECT THE CURRENT ADDITION PER THE WPB |
| | AMENDMENTS TO THE FBC SEC.102.3 APPLICATION OF |
| | REFERENCES. |
| | |
| | 2. ON SHEET A-0.4, FOR FIGURE 604.2, THE WATER CLOSET |
| | LOCATION IS MISSING THE 16" PER THE 2020 ACCESSIBILITY |
| | CODE SECTION 604.2. |
| | |
| | 3. ON SHEET A-2.3; |
| | A. THE TOILET FROM THE WALL HAS A 1'-6," AND PER THE |
| | 2020 FBC ACC 604.2, IT IS ALLOWED TO BE 1'-4" PLEASE |
| | ADD ON BOTH TYPICAL ADA, KEYNOTE A, DETAIL ONE AND R.R. |
| | PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | B. THE HORIZONTAL GRAB BARS NEED TO BE MEASURED TO THE |
| | CENTER OF THE BAR PER THE 2020 FBC ACC SEC. 604.5.1 |
| | SIDE WALL AND 604.5.2 REAR WALL. |
| | |
| | C. PLEASE SHOW THE DIMENSIONS FOR THE WATER CLOSET, |
| | LAVATORY, AND TURNING RADIUS PER THE 2020 FBC ACC SEC. |
| | 606.2. 2 CLEAR FLOOR SPACE. |
| | |
| | D. THE TOP OF THE TOILET SET IS MISSING MIN 15" PER THE |
| | 2020 FBC ACC SEC. 604.4 SEATS. |
| | |
| | 4. ON SHEET P-1.0, SAMPLING PORT NOT APPROVED, PLEASE |
| | PROVIDE A SHIER APPROVED SPECS AS A DEFERED SUBMITAL OR |
| | USE A 4" TWO-WAY CLEAN-OUT AS IT IS AN APPROVED |
| | PRODUCT. ADDITIONALLY, I WILL CROSS OUT SAMPLING POINT |
| | DETAIL AND VERBIAGE THAT PERTAIN TO ITS USE AND |
| | INSTALLATION PER THE WPB AMENDMENTS TO THE FBC SEC. |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 5. 5. ON SHEET P-2.0; |
| | A. THE THREE-COMPARTMENT SINK IS SHOWN CONNECTED INLINE |
| | TO ONE DRAIN. PLEASE INDICATE AS EACH INDIVIDUAL AS |
| | EACH WELL OF A MULTIPLE-COMPARTMENT SINK SHALL |
| | DISCHARGE INDEPENDENTLY TO A WASTE RECEPTOR PER THE |
| | 2020 FBC SEC. P 802.1.1 FOOD HANDLING. |
| | |
| | B. THE RECIRCULATING PUMP HAS A PUMP. THE VALVE SHOULD |
| | BE ON EACH SIDE PER MOST MANUFACTURES' SPECIFICATIONS; |
| | PLEASE SHOW OR PROVIDE SPECS FOR THE UNIT PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | C. ON THE ISOMERIC FOR THE RECIRCULATING SYSTEM, PLEASE |
| | FOLLOW TABLE C404.5.1 PIPING VOLUME AND MAXIMUM PIPING |
| | LENGTHS FOR COMPLIANCE. |
| | |
| | C. PLEASE PROVIDE A LEGEND FOR PLUMBING THAT SHOWS LINE |
| | TYPES, VALVE, PUMP, ETC., PER THE WPB AMENDMENTS TO THE |
| | FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 6. PLEASE PROVIDE VERBIAGE THAT THE ICE MACHINE SHALL |
| | BE PROTECTED WITH A BACKFLOW DEVICE THAT CONFORMS WITH |
| | ASSE 1024 PER THE 2020 FBC P608.17.1.2. |
| | |
| | 7. THE SERVICE SINK (MOP SINK) SURROUNDING THE WALL |
| | SHALL BE A NON-ABSORBENT SURFACE IN ACCORDANCE WITH THE |
| | 2020 FBC BUILDING SEC. 1210.2.2 AND 2020 FBC SEC. P |
| | 310.3. PLEASE MAKE A NOTE ON THIS SHEET. |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION, |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| | |
| | LUIS A. CRESPO |
| | PLUMBING PLAN EXAMINER / INSPECTOR |
| | EMAIL: [email protected] OFFICE: 561 805-6720 |
| | |