Plan Review Notes
Plan Review Notes For Permit 21041392
Permit Number 21041392
Review Stop P
Sequence Number 1
Notes
Date Text
2021-05-13 13:25:1605/13/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
  
 1. ON SHEET A-0.0, UNDER SUBMITTAL NOTES ITEM #1, THE
 CODE REFERENCE USED REFERS TO THE 2017 6TH EDITION.
 PLEASE CORRECT THE CURRENT ADDITION PER THE WPB
 AMENDMENTS TO THE FBC SEC.102.3 APPLICATION OF
 REFERENCES.
  
 2. ON SHEET A-0.4, FOR FIGURE 604.2, THE WATER CLOSET
 LOCATION IS MISSING THE 16" PER THE 2020 ACCESSIBILITY
 CODE SECTION 604.2.
  
 3. ON SHEET A-2.3;
 A. THE TOILET FROM THE WALL HAS A 1'-6," AND PER THE
 2020 FBC ACC 604.2, IT IS ALLOWED TO BE 1'-4" PLEASE
 ADD ON BOTH TYPICAL ADA, KEYNOTE A, DETAIL ONE AND R.R.
 PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 B. THE HORIZONTAL GRAB BARS NEED TO BE MEASURED TO THE
 CENTER OF THE BAR PER THE 2020 FBC ACC SEC. 604.5.1
 SIDE WALL AND 604.5.2 REAR WALL.
  
 C. PLEASE SHOW THE DIMENSIONS FOR THE WATER CLOSET,
 LAVATORY, AND TURNING RADIUS PER THE 2020 FBC ACC SEC.
 606.2. 2 CLEAR FLOOR SPACE.
  
 D. THE TOP OF THE TOILET SET IS MISSING MIN 15" PER THE
 2020 FBC ACC SEC. 604.4 SEATS.
  
 4. ON SHEET P-1.0, SAMPLING PORT NOT APPROVED, PLEASE
 PROVIDE A SHIER APPROVED SPECS AS A DEFERED SUBMITAL OR
 USE A 4" TWO-WAY CLEAN-OUT AS IT IS AN APPROVED
 PRODUCT. ADDITIONALLY, I WILL CROSS OUT SAMPLING POINT
 DETAIL AND VERBIAGE THAT PERTAIN TO ITS USE AND
 INSTALLATION PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 5. 5. ON SHEET P-2.0;
 A. THE THREE-COMPARTMENT SINK IS SHOWN CONNECTED INLINE
 TO ONE DRAIN. PLEASE INDICATE AS EACH INDIVIDUAL AS
 EACH WELL OF A MULTIPLE-COMPARTMENT SINK SHALL
 DISCHARGE INDEPENDENTLY TO A WASTE RECEPTOR PER THE
 2020 FBC SEC. P 802.1.1 FOOD HANDLING.
  
 B. THE RECIRCULATING PUMP HAS A PUMP. THE VALVE SHOULD
 BE ON EACH SIDE PER MOST MANUFACTURES' SPECIFICATIONS;
 PLEASE SHOW OR PROVIDE SPECS FOR THE UNIT PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 C. ON THE ISOMERIC FOR THE RECIRCULATING SYSTEM, PLEASE
 FOLLOW TABLE C404.5.1 PIPING VOLUME AND MAXIMUM PIPING
 LENGTHS FOR COMPLIANCE.
  
 C. PLEASE PROVIDE A LEGEND FOR PLUMBING THAT SHOWS LINE
 TYPES, VALVE, PUMP, ETC., PER THE WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 6. PLEASE PROVIDE VERBIAGE THAT THE ICE MACHINE SHALL
 BE PROTECTED WITH A BACKFLOW DEVICE THAT CONFORMS WITH
 ASSE 1024 PER THE 2020 FBC P608.17.1.2.
  
 7. THE SERVICE SINK (MOP SINK) SURROUNDING THE WALL
 SHALL BE A NON-ABSORBENT SURFACE IN ACCORDANCE WITH THE
 2020 FBC BUILDING SEC. 1210.2.2 AND 2020 FBC SEC. P
 310.3. PLEASE MAKE A NOTE ON THIS SHEET.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION,
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  