Plan Review Notes
Plan Review Notes For Permit 21041392
Permit Number 21041392
Review Stop M
Sequence Number 1
Notes
Date Text
2021-05-07 10:57:441ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21041392
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE SHOW THAT THE RETURN AIR GRILLE FOR RTU-2 AND
 RTU-1 MEETS FBC M 601.5
 601.5 RETURN AIR OPENINGS. RETURN AIR OPENINGS FOR
 HEATING, VENTILATION AND AIR-CONDITIONING SYSTEMS SHALL
 COMPLY WITH ALL
 OF THE FOLLOWING:
  
 1. OPENINGS SHALL NOT BE LOCATED LESS THAN 10 FEET
 (3048 MM) MEASURED IN ANY DIRECTION FROM AN OPEN
 COMBUSTION CHAMBER OR DRAFT HOOD OF ANOTHER APPLIANCE
 LOCATED IN THE SAME ROOM OR SPACE.
  
 7. RETURN AIR SHALL NOT BE TAKEN FROM A CLOSET, TOILET
 ROOM, KITCHEN, GARAGE, BOILER ROOM, FURNACE ROOM OR
 UNCONDITIONED ATTIC.
  
 2) PLEASE PROVIDE OUTDOOR AIR CALCULATIONS FOR EACH USE
 OF SPACE I.E. KITCHEN, DINING ROOM OR FAST FOOD. THE
 OUTDOOR AIR SUBMITTED SEEMS LOW. WE DO NOT USE THE
 ARCHITECTURAL OCCUPANCY NUMBERS WHEN WORKING THE
 CALCULATIONS. FBC M 403.3.1.1 & TABLE 403.3.1.1
  
 3) PLEASE PROVIDE A NOTE ON THE DRAWINGS INDICATING
 THAT THE REFRIGERATION EQUIPMENT MUST BE SUBMITTED
 SEPARATELY FOR A PERMIT AND REVIEW.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  