| 2021-05-07 10:57:44 | 1ST REVIEW FBC-2020 MECHANICAL |
| | PERMIT-21041392 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE |
| | FBC M- FLORIDA MECHANICAL CODE |
| | FBC EC- FLORIDA ENERGY CONSERVATION |
| | FBC FG- FLORIDA FUEL GAS |
| | FBC EX- FLORIDA EXISTING BUILDING CODE |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLEASE SHOW THAT THE RETURN AIR GRILLE FOR RTU-2 AND |
| | RTU-1 MEETS FBC M 601.5 |
| | 601.5 RETURN AIR OPENINGS. RETURN AIR OPENINGS FOR |
| | HEATING, VENTILATION AND AIR-CONDITIONING SYSTEMS SHALL |
| | COMPLY WITH ALL |
| | OF THE FOLLOWING: |
| | |
| | 1. OPENINGS SHALL NOT BE LOCATED LESS THAN 10 FEET |
| | (3048 MM) MEASURED IN ANY DIRECTION FROM AN OPEN |
| | COMBUSTION CHAMBER OR DRAFT HOOD OF ANOTHER APPLIANCE |
| | LOCATED IN THE SAME ROOM OR SPACE. |
| | |
| | 7. RETURN AIR SHALL NOT BE TAKEN FROM A CLOSET, TOILET |
| | ROOM, KITCHEN, GARAGE, BOILER ROOM, FURNACE ROOM OR |
| | UNCONDITIONED ATTIC. |
| | |
| | 2) PLEASE PROVIDE OUTDOOR AIR CALCULATIONS FOR EACH USE |
| | OF SPACE I.E. KITCHEN, DINING ROOM OR FAST FOOD. THE |
| | OUTDOOR AIR SUBMITTED SEEMS LOW. WE DO NOT USE THE |
| | ARCHITECTURAL OCCUPANCY NUMBERS WHEN WORKING THE |
| | CALCULATIONS. FBC M 403.3.1.1 & TABLE 403.3.1.1 |
| | |
| | 3) PLEASE PROVIDE A NOTE ON THE DRAWINGS INDICATING |
| | THAT THE REFRIGERATION EQUIPMENT MUST BE SUBMITTED |
| | SEPARATELY FOR A PERMIT AND REVIEW. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |