| 2021-04-29 15:42:19 | CONDO REMODEL | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected]. | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) DRAWING A1.12 SHOWS THAT THE ELEVATOR LOBBY DOOR IS | | | TO BE REMOVED - ELEVATOR HOISTWAY NEEDS TO BE PROTECTED | | | FBC 3006.2 (5) - PLEASE SHOW HOW ELEVATOR HOISTWAY IS | | | TO BE PROTECTED PER FBC 3006.3 | | | 2) DRAWINGS NEED TO BE SIGNED BY THE DESIGNER FBC | | | 107.2.1 ALL INFORMATION, DRAWINGS, | | | SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE | | | NAME AND SIGNATURE OF THE PERSON | | | RESPONSIBLE FOR THE DESIGN. |
|