Plan Review Notes
Plan Review Notes For Permit 21041347
Permit Number 21041347
Review Stop FIRE
Sequence Number 3
Notes
Date Text
2021-05-21 10:15:12THE PREVIOUS FIRE COMMENTS DO NOT APPEAR TO BE
 SPECIFICALLY ADDRESSED.
  
 THIS PERMIT WILL BE PASSED WITH PROVISO COMMENTS THAT
 WILL BE REVIEWED DURING FIRE INSPECTIONS.
  
 THE PREVIOS COMMENTS ARE SUBMITTAL BELOW AS PROVISO:
  
  
 1) THERE IS AN INDICATION OF A FIRE ALARM RELAY.
  
 WHAT IS THE SEQUENCE OF OPERATION FOR THE FA RELAY?
  
  
 2) THERE IS NO INDICATIONA A KNOX KEY SWITCH.
  
 HOW DOES THE FD GAIN ACCESS IN EMERGENCY SIUATIONS NOT
 RELATED TO THE ACTIVATION OF A FIRE ALARM(PER # 1 ABOVE
 IF THE GATE OPENS ON FIRE ALARM)?
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]