Plan Review Notes
Plan Review Notes For Permit 21041347
Permit Number 21041347
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2021-05-03 13:33:00THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE IS AN INDICATION OF A FIRE ALARM RELAY.
  
 WHAT IS THE SEQUENCE OF OPERATION FOR THE FA RELAY?
  
  
 2) THERE IS NO INDICATIONA A KNOX KEY SWITCH.
  
 HOW DOES THE FD GAIN ACCESS IN EMERGENCY SIUATIONS NOT
 RELATED TO THE ACTIVATION OF A FIRE ALARM(PER # 1 ABOVE
 IF THE GATE OPENS ON FIRE ALARM)?
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL