| Notes |
| Date |
Text |
| 2021-05-03 13:33:00 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1) THERE IS AN INDICATION OF A FIRE ALARM RELAY. | | | | | | WHAT IS THE SEQUENCE OF OPERATION FOR THE FA RELAY? | | | | | | | | | 2) THERE IS NO INDICATIONA A KNOX KEY SWITCH. | | | | | | HOW DOES THE FD GAIN ACCESS IN EMERGENCY SIUATIONS NOT | | | RELATED TO THE ACTIVATION OF A FIRE ALARM(PER # 1 ABOVE | | | IF THE GATE OPENS ON FIRE ALARM)? | | | | | | | | | | | | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|