Plan Review Notes
Plan Review Notes For Permit 21041308
Permit Number 21041308
Review Stop SIGNATURE
Sequence Number 3
Notes
Date Text
2022-01-18 17:16:59SHEET S-1 COMPLIES BUT THE SITE PLAN BY CONTRACTOR DOES
 NOT COMPLY WITH CERTIFICATION BY CONTRACTOR. 107.3.4.3.
 THE CONTRACTOR (QUALIFIER) THAT CREATED / DREW THE SET
 OF PLANS WILL NEED TO IDENTIFY THEMSELVES AS THE AUTHOR
 OF THE PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR NAME
 AND LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED IN
 AND PLANS DRAWN.