Plan Review Notes
Plan Review Notes For Permit 21041308
Permit Number 21041308
Review Stop B
Sequence Number 1
Notes
Date Text
2021-06-03 12:33:39WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21041308
 ADD: 3700 S. DIXIE HWY.
 CONT: FOWLER BUILDING COMPANY
 TEL: 772-486-5350
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: 6/03/2021
 ACTION: DENIED
  
 1) VALUE OF JOB. 109.3 BUILDING PERMIT VALUATION. IF,
 IN THE OPINION OF THE BUILDING OFFICIAL, THE CLAIMED
 VALUATION OF BUILDING, ALTERATION APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE TOTAL REPLACEMENT PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE THE TOTAL
 REPLACEMENT VALUE TO INCLUDE STRUCTURAL, ARCHITECTURAL
 AND DESIGN FEES, MARKETING COST, OVERHEAD AND PROFIT,
 EXCLUDING ONLY LAND VALUE. VALUATION REFERENCES MAY
 INCLUDE THE LATEST PUBLISHED DATA OF NATIONAL
 CONSTRUCTION COST ANALYSIS SERVICES (MARSHALL-SWIFT,
 MEANS, ETC.) WITH REGIONAL ADJUSTMENTS FOR LOCATION AS
 PUBLISHED BY THE INTERNATIONAL CODE CONGRESS.
  
 2) THE SURVEY DOES NOT SHOW THE PROPOSED DECK LOCATION
 ON THE SURVEY. IF THIS IS AN EXISTING DECK AND REPAIR
 IT SHOULD HAVE SHOWN UP ON THE SURVEY. 107.2.1.2
 ADDITIONAL INFORMATION IS REQUIRED.
  
 3) LOOKING THROUGH COMMUNITY PLUS BACK TO 2004 FOR THE
 ADDRESS 3700 S. DIXIE HWY. THERE WAS NEVER A PERMIT
 PULLED FOR ANY DECK CONSTRUCTION. THE SURVEY WAS DATED
 2/03/2010 AND NOTED A PAVER BRICK PATIO. WITH NO PERMIT
 PULLED THIS IS AN ILLEGAL DECK TO BE CONSIDERED NEW
 WORK.
 2020 EXISTING BUILDING CODE LEVEL II 801.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING. CREATION OR EXTENSION
 OF NONCONFORMITY. ALL NEW WORK, RE-CONFIGURATION SHALL
 NOT CREATE OR EXTEND ANY NONCONFORMITY IN THE EXISTING
 BUILDING TO WHICH THE RE-CONFIGURATION OF SPACE IS
 BEING MADE WITH REGARD TO ACCESSIBILITY, STRUCTURAL
 STRENGTH, FIRE SAFETY, MEANS OF EGRESS, OR THE CAPACITY
 OF MECHANICAL, PLUMBING, OR ELECTRICAL SYSTEMS.
  
 4) PLEASE SUBMIT A SITE PLAN SHOWING THE LOCATION OF
 THE BUILDING, IDENTIFY THE TENANT SPACE # 3 SINCE THIS
 PERMIT IS BEING PULLED UNDER THAT TENANT ADDRESS.
 PLEASE ALSO INCLUDE A LETTER FROM THE OWNERS (MARA
 MANAGEMENT LLC) ON THE OWNERS LETTERHEAD THEIR APPROVAL
 OF THE DECK ( PROVIDE SQUARE FEET OF DECK) AND THEIR
 NOTARIZED SIGNATURE. 107.2.1.2. ADDITIONAL INFORMATION
 IS REQUIRED.
  
 5) THEE DECK CAD SHEET PROVIDED DOES NOT INDICATE ANY
 INFORMATION ON THE DECK. SINCE IT IS A WOOD DECK IT IS
 ALSO A RAISED DECK. NO INFORMATION IS GIVEN AS TO THE
 FOUNDATION OF THE DECK, SIZE OF FOOTERS & REINFORCING,
 IF VERTICAL PIERS WERE USED, A FRAMING MEMBER OF THE
 RIM JOIST, FLOOR JOIST, IF PRESSURE TREATED, SIZE,
 SPACING, SPAN, GRADE OF LUMBER, IF MID-SPAN BLOCKING
 WAS INSTALLED, STRAPS FROM THE FOUNDATION TO FRAMING
 MEMBERS, TYPE OF LUMBER IF PRESSURE TREATED, USED FOR
 THE DECKING MATERIAL, SIZE OF DECK MEMBERS.
  
 6A) THE PLAN IS ALSO SILENT AS TO WHAT OCCUPANT LOAD
 FACTOR WAS USED FOR AN OCCUPANT LOAD SINCE THIS PLAN
 NEEDS TO SHOW IT IS UNDER THE 2020 FBC-B NOTE SO ON THE
 PLAN. THE OCCUPANCY NEEDS TO BE DETERMINED. SINCE IT
 CAME IN UNDER TENANT SPACE 3, SEAN RUSH ATELIER INC. AN
 ART GALLERY IS THIS AREA TO BE CONSIDERED AN ASSEMBLY
 AREA? WITH SEATING PLEASE PROVIDE THE OCCUPANT LOADS
 USING TABLE 1004.5 FOR STANDING AND FOR BENCH SEATING.
  
 6B) IS THIS TO BE CONSIDERED AN A2 OCCUPANCY WHERE
 DRINKS ARE TO BE SERVED? 107.2.1.2. ADDITIONAL
 INFORMATION IS REQUIRED.
  
 7) PLEASE ALSO REVIEW IN THE 2020 FBC-B TABLE 1607.1(4)
 LIVE LOADS FOR ASSEMBLY USAGE @ 150 PSF FOR PLATFORMS.
 PLEASE ALSO NOTE THESE PLANS WILL NEED TO BE COMPLETED
 BY AN ENGINEER FOR THE LOADING AND SPACING OF ALL
 FRAMING MEMBERS.
  
 8) THE PLANS DO NOT INDICATE COMPLIANCE WITH THE 2020
 FBC-ACCESSIBILITY CODE FOR ACCESSIBILITY, RAMPS WILL BE
 REQUIRED 1 POSSIBLE 2 IF THE OCCUPANT LOAD IS OVER 49
 OCCUPANTS. RAMPS WILL NEED TO SHOW COMPLIANCE WITH THE
 2020 FBC-ACCESSIBILITY CODE AND SECTIONS OF 405 OF THE
 ACCESSIBILITY CODE INCLUDING HANDRAILS AND EDGE
 PROTECTION.
  
 9) PLEASE ALSO INCLUDE IN THE DRAWINGS AN END DETAIL OR
 CUT SECTION THROUGH THE DECKING MATERIAL TO SHOW HOW
 CLOSE THE WOOD DECKING MEMBERS ARE TO EACH OTHER.
 PLEASE ALSO TAKE INTO ACCOUNT THE SHRINKAGE FACTOR OF
 WOOD DECKS AND THE SOUTH FLORIDA SUN. PLEASE SHOW
 COMPLIANCE WITH THE 2020 FBC-ACCESSIBILITY CODE SECTION
 302. 3 ELONGATED OPENINGS IN FLOORING.
  
 10) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/
 RETIRED.
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
2021-05-21 12:54:53PLEASE CHECK THE USE OF THIS DECK.
 THEY MAY NEED A CHANGE OF OCCUPANCY IF IT IS FOR
 RESTAURANT.