| 2021-06-03 12:33:39 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| | SERVICES/ BUILDING DIVISION |
| | 2020 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 21041308 |
| | ADD: 3700 S. DIXIE HWY. |
| | CONT: FOWLER BUILDING COMPANY |
| | TEL: 772-486-5350 |
| | E-MAIL: [email protected] |
| | |
| | 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: 6/03/2021 |
| | ACTION: DENIED |
| | |
| | 1) VALUE OF JOB. 109.3 BUILDING PERMIT VALUATION. IF, |
| | IN THE OPINION OF THE BUILDING OFFICIAL, THE CLAIMED |
| | VALUATION OF BUILDING, ALTERATION APPEARS TO BE |
| | UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE |
| | DENIED. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS |
| | AND SYSTEMS SHALL BE TOTAL REPLACEMENT PURPOSES, |
| | VALUATION OF BUILDINGS AND SYSTEMS SHALL BE THE TOTAL |
| | REPLACEMENT VALUE TO INCLUDE STRUCTURAL, ARCHITECTURAL |
| | AND DESIGN FEES, MARKETING COST, OVERHEAD AND PROFIT, |
| | EXCLUDING ONLY LAND VALUE. VALUATION REFERENCES MAY |
| | INCLUDE THE LATEST PUBLISHED DATA OF NATIONAL |
| | CONSTRUCTION COST ANALYSIS SERVICES (MARSHALL-SWIFT, |
| | MEANS, ETC.) WITH REGIONAL ADJUSTMENTS FOR LOCATION AS |
| | PUBLISHED BY THE INTERNATIONAL CODE CONGRESS. |
| | |
| | 2) THE SURVEY DOES NOT SHOW THE PROPOSED DECK LOCATION |
| | ON THE SURVEY. IF THIS IS AN EXISTING DECK AND REPAIR |
| | IT SHOULD HAVE SHOWN UP ON THE SURVEY. 107.2.1.2 |
| | ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 3) LOOKING THROUGH COMMUNITY PLUS BACK TO 2004 FOR THE |
| | ADDRESS 3700 S. DIXIE HWY. THERE WAS NEVER A PERMIT |
| | PULLED FOR ANY DECK CONSTRUCTION. THE SURVEY WAS DATED |
| | 2/03/2010 AND NOTED A PAVER BRICK PATIO. WITH NO PERMIT |
| | PULLED THIS IS AN ILLEGAL DECK TO BE CONSIDERED NEW |
| | WORK. |
| | 2020 EXISTING BUILDING CODE LEVEL II 801.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. CREATION OR EXTENSION |
| | OF NONCONFORMITY. ALL NEW WORK, RE-CONFIGURATION SHALL |
| | NOT CREATE OR EXTEND ANY NONCONFORMITY IN THE EXISTING |
| | BUILDING TO WHICH THE RE-CONFIGURATION OF SPACE IS |
| | BEING MADE WITH REGARD TO ACCESSIBILITY, STRUCTURAL |
| | STRENGTH, FIRE SAFETY, MEANS OF EGRESS, OR THE CAPACITY |
| | OF MECHANICAL, PLUMBING, OR ELECTRICAL SYSTEMS. |
| | |
| | 4) PLEASE SUBMIT A SITE PLAN SHOWING THE LOCATION OF |
| | THE BUILDING, IDENTIFY THE TENANT SPACE # 3 SINCE THIS |
| | PERMIT IS BEING PULLED UNDER THAT TENANT ADDRESS. |
| | PLEASE ALSO INCLUDE A LETTER FROM THE OWNERS (MARA |
| | MANAGEMENT LLC) ON THE OWNERS LETTERHEAD THEIR APPROVAL |
| | OF THE DECK ( PROVIDE SQUARE FEET OF DECK) AND THEIR |
| | NOTARIZED SIGNATURE. 107.2.1.2. ADDITIONAL INFORMATION |
| | IS REQUIRED. |
| | |
| | 5) THEE DECK CAD SHEET PROVIDED DOES NOT INDICATE ANY |
| | INFORMATION ON THE DECK. SINCE IT IS A WOOD DECK IT IS |
| | ALSO A RAISED DECK. NO INFORMATION IS GIVEN AS TO THE |
| | FOUNDATION OF THE DECK, SIZE OF FOOTERS & REINFORCING, |
| | IF VERTICAL PIERS WERE USED, A FRAMING MEMBER OF THE |
| | RIM JOIST, FLOOR JOIST, IF PRESSURE TREATED, SIZE, |
| | SPACING, SPAN, GRADE OF LUMBER, IF MID-SPAN BLOCKING |
| | WAS INSTALLED, STRAPS FROM THE FOUNDATION TO FRAMING |
| | MEMBERS, TYPE OF LUMBER IF PRESSURE TREATED, USED FOR |
| | THE DECKING MATERIAL, SIZE OF DECK MEMBERS. |
| | |
| | 6A) THE PLAN IS ALSO SILENT AS TO WHAT OCCUPANT LOAD |
| | FACTOR WAS USED FOR AN OCCUPANT LOAD SINCE THIS PLAN |
| | NEEDS TO SHOW IT IS UNDER THE 2020 FBC-B NOTE SO ON THE |
| | PLAN. THE OCCUPANCY NEEDS TO BE DETERMINED. SINCE IT |
| | CAME IN UNDER TENANT SPACE 3, SEAN RUSH ATELIER INC. AN |
| | ART GALLERY IS THIS AREA TO BE CONSIDERED AN ASSEMBLY |
| | AREA? WITH SEATING PLEASE PROVIDE THE OCCUPANT LOADS |
| | USING TABLE 1004.5 FOR STANDING AND FOR BENCH SEATING. |
| | |
| | 6B) IS THIS TO BE CONSIDERED AN A2 OCCUPANCY WHERE |
| | DRINKS ARE TO BE SERVED? 107.2.1.2. ADDITIONAL |
| | INFORMATION IS REQUIRED. |
| | |
| | 7) PLEASE ALSO REVIEW IN THE 2020 FBC-B TABLE 1607.1(4) |
| | LIVE LOADS FOR ASSEMBLY USAGE @ 150 PSF FOR PLATFORMS. |
| | PLEASE ALSO NOTE THESE PLANS WILL NEED TO BE COMPLETED |
| | BY AN ENGINEER FOR THE LOADING AND SPACING OF ALL |
| | FRAMING MEMBERS. |
| | |
| | 8) THE PLANS DO NOT INDICATE COMPLIANCE WITH THE 2020 |
| | FBC-ACCESSIBILITY CODE FOR ACCESSIBILITY, RAMPS WILL BE |
| | REQUIRED 1 POSSIBLE 2 IF THE OCCUPANT LOAD IS OVER 49 |
| | OCCUPANTS. RAMPS WILL NEED TO SHOW COMPLIANCE WITH THE |
| | 2020 FBC-ACCESSIBILITY CODE AND SECTIONS OF 405 OF THE |
| | ACCESSIBILITY CODE INCLUDING HANDRAILS AND EDGE |
| | PROTECTION. |
| | |
| | 9) PLEASE ALSO INCLUDE IN THE DRAWINGS AN END DETAIL OR |
| | CUT SECTION THROUGH THE DECKING MATERIAL TO SHOW HOW |
| | CLOSE THE WOOD DECKING MEMBERS ARE TO EACH OTHER. |
| | PLEASE ALSO TAKE INTO ACCOUNT THE SHRINKAGE FACTOR OF |
| | WOOD DECKS AND THE SOUTH FLORIDA SUN. PLEASE SHOW |
| | COMPLIANCE WITH THE 2020 FBC-ACCESSIBILITY CODE SECTION |
| | 302. 3 ELONGATED OPENINGS IN FLOORING. |
| | |
| | 10) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| | REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| | REVIEW CYCLE. |
| | PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID |
| | 19 |
| | IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS |
| | 561-718-9724. |
| | WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/ |
| | RETIRED. |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES |
| | DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| 2021-05-21 12:54:53 | PLEASE CHECK THE USE OF THIS DECK. |
| | THEY MAY NEED A CHANGE OF OCCUPANCY IF IT IS FOR |
| | RESTAURANT. |