Plan Review Notes
Plan Review Notes For Permit 21041294
Permit Number 21041294
Review Stop P
Sequence Number 1
Notes
Date Text
2021-06-09 14:49:241ST REVIEW FBC-2020 RES. PLUMBING
 PERMIT- 21041294
 6/9/2021
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE PLUMBING CONTRACTOR M. COSTA SHALL PROVIDE A
 SUB-PERMIT APPLICATION, AND SHALL ALSO PROVIDE HIS OR
 HER SIGNATURE ON THE PLUMBING PLANS- SECTION 105.1,
 107.2.1 WPB AMENDMENTS TO THE FBC AND FLORIDA STATUTES
 471.003(2)(H) & 471.025.
  
 2) PLEASE PROVIDE AN ITEMIZED SCOPE OF PLUMBING WORK
 OUTLINE FOR THE PROPOSED PROJECT- SECTION 107.2.1 WPB.
 LABEL THE PLUMBING FIXTURES AND PIPING SHOWN ON THE
 PLANS AND EITHER NEW OR EXISTING. PROVIDE A LIST OF
 PLUMBING FIXTURES AND APPLIANCES BEING REPLACED,
 RELOCATED, OR NEWLY INSTALLED- SECTION 107.2.1 WPB.
  
 3) PROVIDE A SANITARY DRAINAGE AND VENT ISOMETRIC
 DRAWING- SECTION 107.3.5.3 WPB AMENDMENTS TO THE FBC.
  
 4) IDENTIFY THE LOCATION OF THE REQUIRED CLEANOUT AT
 THE JUNCTION OF THE BUILDING AND SEWER DRAINS- SECTION-
 P3005.2.3 FBC RES.
  
 5) THE PLAN APPEARS TO SHOW 2 -INCH FIXTURE BRANCH
 DRAINS FROM THE WASHING MACHINES, HOWEVER 3-INCH DRAINS
 ARE REQUIRED- SECTION 406.2 FBC P.
  
 6) PLEASE NOTE THIS IS A MULTI-FAMILY DWELLING, AND A
 BACKFLOW PREVENTION ASSEMBLY IS REQUIRED AT THE POINT
 OF DELIVERY. PLEASE CLARIFY IF THERE IS AN EXISTING BF
 ASSEMBLY IN USE. THE TYPE OF BACKFLOW ASSEMBLY REQUIRED
 WILL BE DEPENDENT UPON THE DEGREE OF HAZARD POSED BY
 THE WATER USER. A REDUCED PRESSURE ZONE BACKFLOW DEVICE
 IS REQUIRED BY THE CITY OF WEST PALM CROSS UTILITIES
 DEPARTMENT AND THEIR CONNECTION CONTROL PROGRAM.
 PLEASE NOTE THAT A FL. LICENSED PLUMBING CONTRACTOR
 SHALL OBTAIN A SEPARATE PERMIT FOR INSTALLATION OF THE
 BACKFLOW PREVENTER IN ACCORDANCE WITH SECTION 105.1 WPB
 AND SEC. 90-33 WPB CODE OF ORDINANCES. THE DEVICE SHALL
 BE TESTED AND CERTIFIED BY THE WPB UTILITIES DEPARTMENT
 PRIOR TO FINAL INSPECTION BY THE BUILDING DEPARTMENT.
 PLEASE CONTACT THE WPB UTILITIES CENTRAL OPERATIONS
 DEPT.AT 561-822-2210 FOR FURTHER INFORMATION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  