| 2021-05-05 10:27:13 | 1ST REVIEW FBC-2020 RES. PLUMBING | | | PERMIT- 21041290 | | | 5/5/2021 | | | | | | CODES IN EFFECT: | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | | 2020 | | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION | | | 2020 | | | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET P-101: PLEASE CORRECT THE PLUMBING RISER | | | SHOWING A VENT PIPE CONNECTION TO THE AAV- SECTION | | | P3114.2 & P3114.3 FBC RES. | | | | | | 2) P-101: LOCATION OF THE AAV SHALL BE MINIMUM 4 INCHES | | | ABOVE THE FIXTURE DRAIN- PLEASE ADD THE DIMESNION OR | | | NOTE AT THE DETAIL- SECTION P3114.4 FBC RES. | | | | | | 3) PROVIDE A PLUMBING SUB-PERMIT APPLICATION- SECTION | | | 105.1 WPB. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | |
|