| Plan Review Notes For Permit 21041281 |
| Permit Number |
21041281 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-04-28 11:40:13 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) THERE ARE INDICATIONS ON SEVERAL PLAN SHEETS OF A | | | CHASE CONTAINING ELECT., MED. GAS, ETC FROM 1ST FLOOR | | | TO THE 3RD FLOOR. | | | | | | IT INDICATES THAT CONTRACTOR TO VERIFY THIS CHASE IS 1 | | | HOUR RATED; HOWEVER, IT DOES NOT INDICATE THAT IS, IN | | | FACT, 1HR RATED. | | | | | | PLEASE PROVIDED DETAILED FACTUAL INFORMATION THAT THIS | | | CHASE IS RATED 1 HOUR AND PROVIDE THE VERIFIED NOTE. | | | | | | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|