| 2021-08-17 14:32:19 | 3RD REVIEW FBC-2020 MECHANICAL |
| | PERMIT-21041277 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE |
| | FBC M- FLORIDA MECHANICAL CODE |
| | FBC EC- FLORIDA ENERGY CONSERVATION |
| | FBC FG- FLORIDA FUEL GAS |
| | FBC EX- FLORIDA EXISTING BUILDING CODE |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET M4.0: PER FBC M 403.3.1.1 AND TABLE 403.3.1.1 |
| | AND THE SQUARE FOOTAGE GIVEN FROM THE DESIGNER FOR THE |
| | OUTDOOR AIR CALCULATIONS THE FOLLOWING ARE THE REQUIRED |
| | OUTDOOR AIR CALCULATIONS REQUIRED FOR THE USE OF SPACE. |
| | |
| | KITCHEN: 490/1000 = .49 X 20 = 9.8 PEOPLE X 7.5 = 73.5 |
| | + 490 X .12 = 132.3 REQUIRED FOR OUTDOOR AIR. KITCHEN |
| | EXHAUST: 490 X .7 = 343 CFM OF EXHAUST. |
| | |
| | WORKROOM WHICH IS LOCATED IN THE KITCHEN WITH NO |
| | SEPARATION MUST BE COUNTED AS KITCHEN: 229/1000 = .229 |
| | X 20 = 4.58 PEOPLE X 7.5 = 34.35 + 229 X .12 = 61.83 |
| | CFM OF REQUIRED OUTDOOR AIR. KITCHEN EXHAUST: 229 X .7 |
| | = 160 CFM OF EXHAUST. |
| | |
| | SEATING AREA: 195/1000 = .195 X 70 = 13.65 PEOPLE X 7.5 |
| | = 102.38 + 195 X .18 = 138.02 OF REQUIRED OUTDOOR AIR. |
| | |
| | KITCHEN PREP: 123/1000 = .123 X 20 = 2.46 PEOPLE X 7.5 |
| | = 18.45 + 123 X .12 = 33.21 CFM OF REQUIRED OUTDOOR |
| | AIR. KITCHEN EXHAUST: 123 X .7 = 86 CFM OF EXHAUST. |
| | |
| | IF SQUARE FOOTAGE IS NOT NET PLEASE SEE FOOTNOTE (A ) |
| | FBC M TABLE 403.3.1.1 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |