| Date |
Text |
| 2021-07-13 16:10:44 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1 |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION |
| | FBC FG = FLORIDA FUEL GAS CODE 2020 7TH EDITION |
| | NFPA 54 = NATIONAL FUEL GAS CODE |
| | NFPA 96 = STANDARD FOR VENTILATION CONTROL AND FIRE |
| | PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017FAC= |
| | FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | |
| | 2ND REVIEW |
| | PLUMBING COMMENTS: DENIED |
| | |
| | PROVISO: WATER HEATER SCHEDULE INDICATES THAT AN |
| | ALTERNATE MANUFACTURER MAY BE SUBMITTED TO A/E FOR |
| | APPROVAL AND USE. PLEASE NOTE THAT A MANUFACTURER'S |
| | SPECIFICATION/INSTALLATION MANUAL SHALL BE SUBMITTED TO |
| | THE BUILDING DEPARTMENT FOR REVIEW AND APPROVAL AND IF |
| | DIFFERENT FROM THE CURRENT SCHEDULE A PLAN REVISION |
| | SHALL BE SUBMITTED TO THE BUILDING DEPARTMENT FOR |
| | REVIEW AND APPROVAL. BOTH SHALL BE ON SITE FOR FINAL |
| | INSPECTION. SEE WPB FBC 107.2.1 AND WPB FBC 107.3.4.1, |
| | DEFERRED SUBMITTALS. PROCEED AT YOUR OWN RISK. |
| | |
| | 1. SECOND REQUEST: PER FBC 606.5 EXPOSED PIPES AND |
| | SURFACES. WATER SUPPLY & DRAINPIPES UNDER LAVATORIES |
| | AND SINKS SHALL BE INSULATED OR OTHERWISE CONFIGURED TO |
| | PROTECT AGAINST CONTACT. PLANS SHOW INSULATED P-TRAP |
| | BUT DO NOT INDICATE WATER SUPPLY PIPES. |
| | |
| | 2.SECOND REQUEST: PER WPB FBC 107.2.1, PROVIDE |
| | STRUCTURAL DETAIL FOR MOUNTING OF THE TANKLESS WATER |
| | HEATER. |
| | |
| | 3. SECOND REQUEST: PER FBC PL 419.5, COLD OR TEMPERED |
| | WATER SHALL BE DELIVERED FROM LAVATORIES AND GROUP WASH |
| | FIXTURES LOCATED IN PUBLIC TOILET FACILITIES PROVIDED |
| | FOR CUSTOMERS, PATRONS AND VISITORS. TEMPERED WATER |
| | SHALL BE DELIVERED THROUGH AN APPROVED |
| | WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE |
| | 1070 OR CSA B125.3. |
| | BMC RESPONSE: PLUMBING FIXTURE SCHEDULE HAS BEEN |
| | PROVIDED, WHICH DOES INDICATE THE TEMPERATURE LIMITING |
| | DEVICE FOR LAVATORIES AND HAND SINKS. |
| | NEW COMMENT: CANNOT FIND THE NOTED PLUMBING FIXTURE |
| | SCHEDULE ON THE PLANS. |
| | |
| | 4.NEW COMMENT REGARDING THE WATER METER: PER WPB FBC |
| | 107.2.1, PROVIDE MANUFACTURER?S |
| | SPECIFICATION/INSTALLATION MANUAL; ESPECIALLY SHOW |
| | INTEGRAL BACKFLOW PROTECTION, OR SPECIFY AND PROVIDE |
| | LEAD FREE BACKFLOW PREVENTER |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |
| | |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | MOBILE 561-246-0882 |
| | PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND |
| | THURSDAYS |
| | |
| | 21041277 7402 S DIXIE HWY |
| | |