| 2021-07-13 15:02:40 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1 |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION |
| | FBC FG = FLORIDA FUEL GAS CODE 2020 7TH EDITION |
| | NFPA 54 = NATIONAL FUEL GAS CODE |
| | NFPA 96 = STANDARD FOR VENTILATION CONTROL AND FIRE |
| | PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017FAC= |
| | FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | |
| | 2ND REVIEW |
| | |
| | GAS COMMENTS: DENIED |
| | |
| | 1.WATER HEATER DETAIL; PER WPB FBC 107.2.1, CLARIFY THE |
| | FOLLOWING. |
| | SECOND REQUEST: SHOWS GAS- REGULATOR TO REDUCE PRESSURE |
| | TO 2 PSI. NOTE SHOULD STATE "REDUCE PRESSURE FROM 2 PSI |
| | TO .5 IN. WC" TO MATCH DESCRIPTION OF GAS REGULATOR ON |
| | P0.0 |
| | |
| | 2.SUBMIT CALCULATIONS FOR COMBUSTION AIR (NOT TO BE |
| | CONFUSED WITH MAKE-UP AIR.) PER THE FBC FG 304.1 CALCS |
| | ON P1.0; |
| | NEW COMMENT: AVAILABLE COMBUSTION AIR NOT NOTED. PER |
| | WPB FBC 107.2.1, INDICATE ON THE PLANS THE AVAILABLE |
| | COMBUSTION AIR (EXCESS OUTSIDE AIR MAY PROVIDE,PLEASE |
| | CLARIFY) |
| | |
| | 3.GAS RISER: CLEARLY SHOW THE LOCATION OF ALL MP |
| | (STEP-DOWN) REGULATORS, VALVES AND UNIONS . A LISTED |
| | SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY AHEAD OF |
| | EACH MP REGULATOR. FBC FG 409.4 |
| | NEW COMMENT: PER WPB FBC 107.2.1, PROVIDE NOTE AT |
| | PRESSURE REGULATOR DESCRIPTION ON P0.0; ?INSTALLATION |
| | OF GAS REGULATOR SHALL COMPLY WITH FBC FG 410.2? |
| | |
| | 4.SECOND REQUEST: NOTES ON P0.0 ARE UNCLEAR AS TO |
| | INTENT. WHERE DOES THE 2PSI SYSTEM END AND THE LESS |
| | THAN 2PSI BEGIN. PER WPB FBC 107.2.1, CLARIFY. IS A |
| | REGULATOR TO BE PROVIDED IMMEDIATELY DOWNSTREAM OF THE |
| | FPU METER/ REGULATOR TO REDUCE PRESSURE AND THEN AN |
| | APPLIANCE REGULATOR TO BE SUPPLIED AT THE APPLIANCE; |
| | PER WPB FBC 107.2.1, CLARIFY. PROVIDE TABLES FOR SIZING |
| | FOR (2 PSI 1LB.PRESSURE DROP 402.4(5) #40 METALLIC) AS |
| | WELL AS (LESS THAN 2 PSI 402.4(3) 3? WC) NOTED .. |
| | CLEARLY INDICATE ON THE PIPING PLAN, THE 2 PSI PIPING |
| | AND WHICH GAS NOTE (2 OR 7) APPLIES TO WHICH SECTIONS |
| | OF PIPE. |
| | RESPONSE IS UNCLEAR |
| | ALSO UG IS NOT SPECIFIED-IF PE (PLASTIC PIPING) THEN |
| | PROVIDE TABLE AND TRACER WIRE W/DETAIL FOR TRANSITION |
| | TO AG. |
| | |
| | REVISED COMMENT |
| | P0.0 NOTES |
| | A.NOTED TABLE 402.4(3) ADDRESSES SCHEDULE 40 METALLIC |
| | PIPING LESS THAN 2PSI/.3 IN. WC/0.60 SG |
| | B.TABLE 402.4(2) NOT NOTED ADDRESSES SCHEDULE 40 |
| | METALLIC PIPING LESS THAN 2PSI/.5 IN. WC/0.60 SG WHICH |
| | WOULD SEEM TO MATCH YOUR NOTE FOR THE GAS REGULATOR |
| | DESCRIPTION. |
| | C.NOTED PRESSURE 2PSI/1LB. PRESSURE DROP/0.60 SG FOR |
| | SCHEDULE 40 METALLIC PIPING IS COVERED BY TABLE |
| | 402.4(5) |
| | E.REGARDING UG PIPE FROM METER TO BUILDING AND TO WATER |
| | HEATER, |
| | 1) PLEASE REFER TO FBC FG 411.1, 411.1.1, 411.1.2(1), |
| | (2), (3) FOR PROTECTION OF STEEL PIPING FROM CORROSION |
| | (TABLE 402.4(5) WOULD APPLY). THIS OPTION REQUIRES |
| | STRINGENT AND POSSIBLY VERY EXPENSIVE REQUIREMENTS, |
| | 2) OR REFER TO FBC FG 407.17, 407.17.1, 407.17.2, |
| | 407.17.3 FOR PLASTIC PIPING. FBC FG TABLE 402.4(22) |
| | WOULD APPLY. |
| | |
| | 5. SECOND REQUEST: SUBMIT MANUFACTURER'S SPECIFICATION |
| | SHEETS / INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO |
| | VERIFY COMPLIANCE FBC FG 402.2, AND 301.3. GAS |
| | APPLIANCES SHALL BE LISTED AND LABELED. THE |
| | INSTALLATION MANUALS FOR ALL GAS APPLIANCES / EQUIPMENT |
| | SHALL BE ONSITE AT THE TIME OF INSPECTION. FBC FG 305.1 |
| | NEW COMMENT: YOU MAY PER WPB FBC 107.2.1 AND WPB FBC |
| | 107.3.4.1, PROVIDE AS A DEFERRED SUBMITTAL |
| | MANUFACTURER'S SPECIFICATION SHEETS / INSTALLATION |
| | MANUAL FOR ALL GAS EQUIPMENT TO VERIFY COMPLIANCE FBC |
| | FG 402.2, AND 301.3. GAS APPLIANCES SHALL BE LISTED AND |
| | LABELED. THE INSTALLATION MANUALS FOR ALL GAS |
| | APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF |
| | INSPECTION. FBC FG 305.1. DOCUMENT SHALL BE SUBMITTED, |
| | APPROVED AND ON SITE PRIOR TO FINAL INSPECTION. PROCEED |
| | AT YOUR OWN RISK. PROVIDE NOTE ON THE PLANS. |
| | |
| | 6.SECOND REQUEST: PER WPB FBC 107.2.1, SPECIFY THE |
| | UNDERGROUND PIPING MATERIAL AND PROVIDE SIZING TABLE. |
| | SEE REVISED COMMENT IN NOTE 4 ABOVE. |
| | |
| | 7.PER WPB FBC 107.2.1, EXPLAIN THE DESIGNATION LNG ON |
| | THE RISER DIAGRAM. IS THIS LIQUIFIED NATURAL GAS? |
| | CLARIFY. |
| | NEW COMMENT: LIQUIFIED NATURAL GAS IS A STATE THAT IS |
| | USED FOR TRANSPORT (COMPRESSED BY REDUCING TEMPERATURE |
| | TO -250 DEGREES F AND MAINTAINED AT 4PSI) AND IS NOT |
| | DISTRIBUTED TO THE END USER IN THIS STATE. PER WPB FBC |
| | 107.2.1, REVISE ALL DESIGNATION OF LNG TO NG FOR |
| | NATURAL GAS. |
| | |
| | 8.PER WPB FBC 107.2.1, SHOW LOCATION OF THE FPU |
| | METER/REGULATOR ON THE PLAN VIEW. |
| | NEW COMMENT: PROVIDE GAS SHUT OFF VALVE AT CONSUMER |
| | SIDE OF METER REGULATOR PER FBC FG 409.2 |
| | NEW COMMENT: PER WPB FBC 107.2.1, PROVIDE SPEC FOR GAS |
| | SHUT-OFF VALVES TO COMPLY WITH FBC FG SECTION 409. |
| | |
| | 9.NEW COMMENT: KITCHEN EQUIPMENT SCHEDULE ON P2.0 MBTUS |
| | DOES NOT MATCH THE KITCHEN EQUIPMENT NOTED ON P0.0 GAS |
| | FIXTURE LOAD SUMMARY. PER WPB FBC 107.2.1, CLARIFY AND |
| | RECONCILE. |
| | |
| | |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |
| | |