| | 1ST REVIEW |
| | |
| | GAS COMMENTS: DENIED |
| | |
| | PROVISO: WATER HEATER SCHEDULE INDICATES THAT AN |
| | ALTERNATE MANUFACTURER MAY BE SUBMITTED TO A/E FOR |
| | APPROVAL AND USE. PLEASE NOTE THAT A MANUFACTURER?S |
| | SPECIFICATION INSTALLATION MANUAL SHALL BE SUBMITTED TO |
| | THE BUILDING DEPARTMENT FOR REVIEW AND APPROVAL AND IF |
| | DIFFERENT FROM THE CURRENT SCHEDULE A PLAN REVISION |
| | SHALL BE SUBMITTED TO THE BUILDING DEPARTMENT FOR |
| | REVIEW AND APPROVAL. BOTH SHALL BE ON SITE FOR FINAL |
| | INSPECTION. |
| | |
| | PROVISO: REGULATOR SCHEDULE INDICATES THAT AN ALTERNATE |
| | MANUFACTURER MAY BE SUBMITTED TO A/E FOR APPROVAL AND |
| | USE. PLEASE NOTE THAT A MANUFACTURER?S SPECIFICATION |
| | INSTALLATION MANUAL SHALL BE SUBMITTED TO THE BUILDING |
| | DEPARTMENT FOR REVIEW AND APPROVAL AND IF DIFFERENT |
| | FROM THE CURRENT SCHEDULE A PLAN REVISION SHALL BE |
| | SUBMITTED TO THE BUILDING DEPARTMENT FOR REVIEW AND |
| | APPROVAL. BOTH SHALL BE ON SITE FOR FINAL INSPECTION. |
| | |
| | |
| | 1.WATER HEATER DETAIL; PER WPB FBC 107.2.1, CLARIFY THE |
| | FOLLOWING. |
| | A.SHOWS GAS SUPPLIED FROM FPU TANKS |
| | B.SHOWS GAS- REGULATOR TO REDUCE PRESSURE TO 2 PSI. |
| | |
| | 2.SUBMIT CALCULATIONS FOR COMBUSTION AIR (NOT TO BE |
| | CONFUSED WITH MAKE-UP AIR.) PER FBC FG 304.1 |
| | |
| | 3.GAS RISER: CLEARLY SHOW THE LOCATION OF ALL MP |
| | (STEP-DOWN) REGULATORS, VALVES AND UNIONS . A LISTED |
| | SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY AHEAD OF |
| | EACH MP REGULATOR. FBC FG 409.4 |
| | |
| | 4.NOTES ON P0.0 ARE UNCLEAR AS TO INTENT. WHERE DOES |
| | THE 2PSI SYSTEM END AND THE LESS THAN 2PSI BEGIN. PER |
| | WPB FBC 107.2.1, CLARIFY. IS A REGULATOR TO BE PROVIDED |
| | IMMEDIATELY DOWNSTREAM OF THE FPU METER/ REGULATOR TO |
| | REDUCE PRESSURE AND THEN AN APPLIANCE REGULATOR TO BE |
| | SUPPLIED AT THE APPLIANCE; PER WPB FBC 107.2.1, |
| | CLARIFY. PROVIDE TABLES FOR SIZING FOR 2 PSI AS WELL AS |
| | LESS THAN 2 PSI. CLEARLY INDICATE ON THE PIPING PLAN, |
| | THE 2 PSI PIPING AND WHICH GAS NOTE (2 OR 7) APPLIES TO |
| | WHICH SECTIONS OF PIPE. |
| | |
| | 5.SUBMIT MANUFACTURER?S SPECIFICATION SHEETS / |
| | INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY |
| | COMPLIANCE FBC FG 402.2, AND 301.3. GAS APPLIANCES |
| | SHALL BE LISTED AND LABELED. THE INSTALLATION MANUALS |
| | FOR ALL GAS APPLIANCES / EQUIPMENT SHALL BE ONSITE AT |
| | THE TIME OF INSPECTION. FBC FG 305.1 |
| | |
| | 6.GAS RISER: CLEARLY SHOW THE LOCATION OF THE EMERGENCY |
| | HOOD SHUT DOWN SHUT OFF VALVE SHALL BE BELOW THE |
| | CEILING. THE MANUAL SHUTOFF VALVE SHALL BE UPSTREAM. |
| | UNION TO BE DOWN STREAM OF MANUAL VALVE. SECS. 10.4, |
| | 10.5 OF NFPA 96-08. PROVIDE DETAIL. |
| | |
| | 7.PER WPB FBC 107.2.1, SPECIFY THE UNDERGROUND PIPING |
| | MATERIAL AND PROVIDE SIZING TABLE. |
| | |
| | 8.PER WPB FBC 107.2.1, EXPLAIN THE DESIGNATION LNG ON |
| | THE RISER DIAGRAM. IS THIS LIQUIFIED NATURAL GAS? |
| | CLARIFY. |
| | |
| | 9.WHEN ADDING UP THE MBTU IN THE GAS FIXTURE LOAD |
| | SUMMARY, I COME UP WITH 967 MBH. THE SUMMARY INDICATES |
| | 588 MBH. PER WPB FBC 107.2.1, CLARIFY. |
| | |
| | 10.PER WPB FBC 107.2.1, SHOW LOCATION OF THE FPU |
| | METER/REGULATOR ON THE PLAN VIEW. |
| | |
| | 11.EQUIPMENT SCHEDULE ON P2.0 IS PARTIALLY OBSCURED BY |
| | A STAMP. PER WPB FBC 107.2.1, REMOVE OR RELOCATE THE |
| | STAMP SO THAT THE ENTIRE SCHEDULE IS LEGIBLE. |
| | |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |
| | |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | MOBILE 561-246-0882 |
| | PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND |
| | THURSDAYS |
| | |
| | 21041277 7402 S DIXIE HWY |