2021-04-30 11:02:191ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21041255
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M3.01: PLEASE ADD THE CFM?S OF SUPPLY AIR IN
 OFFICES 109, 110 AND 111 FBC 107.2.1
  
 2) SHEET M6.01 INDICATES THAT VAV-11.10 DESIGN AIR FLOW
 IS 250 CFM. SHEET M3.01 INDICATES IT WILL SUPPLY 870
 CFM, PLEASE ADJUST THIS VAV TO THE REQUIRED SUPPLY AIR.
 FBC 107.2.1
  
 3) SHEET M6.01 INDICATES THAT VAV-11.9 DESIGN AIR FLOW
 IS 970 CFM. SHEET M3.01 INDICATES IT WILL SUPPLY ONLY
 250 CFM, I BELIEVE VAV-11.9 AND VAV-11.10 ARE CROSSED.
 PLEASE CORRECT. FBC 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  