| 2021-04-30 11:02:19 | 1ST REVIEW FBC-2020 MECHANICAL | | | PERMIT-21041255 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE | | | FBC M- FLORIDA MECHANICAL CODE | | | FBC EC- FLORIDA ENERGY CONSERVATION | | | FBC FG- FLORIDA FUEL GAS | | | FBC EX- FLORIDA EXISTING BUILDING CODE | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET M3.01: PLEASE ADD THE CFM?S OF SUPPLY AIR IN | | | OFFICES 109, 110 AND 111 FBC 107.2.1 | | | | | | 2) SHEET M6.01 INDICATES THAT VAV-11.10 DESIGN AIR FLOW | | | IS 250 CFM. SHEET M3.01 INDICATES IT WILL SUPPLY 870 | | | CFM, PLEASE ADJUST THIS VAV TO THE REQUIRED SUPPLY AIR. | | | FBC 107.2.1 | | | | | | 3) SHEET M6.01 INDICATES THAT VAV-11.9 DESIGN AIR FLOW | | | IS 970 CFM. SHEET M3.01 INDICATES IT WILL SUPPLY ONLY | | | 250 CFM, I BELIEVE VAV-11.9 AND VAV-11.10 ARE CROSSED. | | | PLEASE CORRECT. FBC 107.2.1 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | | | 2021-04-30 10:38:03 | | | | | | | |
|