| 2021-05-07 13:53:08 | WINDOWS/DOORS SUBMITTAL BUILDING REVIEW COMMENTS |
| | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| | SUBMITTAL #21041230 |
| | |
| | 1- WINDOW PRODUCT APPROVAL WAS CHANGED TO DOUBLE HUNG |
| | FLORIDA PRODUCT APPROVAL FL14477-R5. THIS PRODUCT |
| | APPROVAL DOESN'T INCLUDE A WINDOW SIZE SCHEDULE. PLANS |
| | SPECIFY SH25 EGRESS WINDOWS FOR THE SECOND FLOOR |
| | BEDROOMS. |
| | TYPICALLY, A SH25 SINGLE HUNG HAS A SIZE OF +/-37" |
| | WIDTH BY +/-63" HEIGHT. BASED ON THE KOLBE & KOLBE |
| | MILLWORK COMPANY WEBSITE IT LOOKS LIKE THIS SIZE OF |
| | WINDOW MAY NOT COMPLY WITH THE EGRESS REQUIREMENTS FOR |
| | THE SECOND FLOOR BEDROOMS. |
| | PROVIDE MANUFACTURER'S CUT SHEETS SHOWING THAT THE |
| | SPECIFIED WINDOW SIZE COMPLIES WITH THE EGRESS |
| | REQUIREMENTS. CLEARLY SHOW SIZE OF WINDOW AND ALL CLEAR |
| | OPENINGS: WIDTH, HEIGHT AND TOTAL CLEAR OPENING. IF |
| | SIZE OF WINDOW NEEDS TO BE REVISED, THEN REVISE PLANS |
| | ACCORDINGLY. |
| | SEC. R310.2.1 FBC-RESIDENTIAL. |
| | |
| | 2- DOUBLE HUNG WINDOW FLORIDA PRODUCT APPROVAL NUMBER |
| | LISTED IN THE ENGINEER'S PRODUCT APPROVAL LETTER |
| | DOESN'T MATCH ONE SUBMITTED. REVISE AS REQUIRED TO |
| | MATCH. |
| | SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | 3- NEED TO SUBMIT ALL THE PRODUCT APPROVALS REQUIRED |
| | FOR THIS HOUSE. ONLY THE ROOFING PRODUCT APPROVALS ARE |
| | ALREADY APPROVED. NOTE: PRODUCT APPROVALS WERE NOT |
| | APPROVED WHEN THE BUILDING PERMIT WAS ISSUED BECAUSE IT |
| | WAS AGREED WITH MRS. SOFIA SCIALLA THAT IN ORDER TO |
| | EXPEDITE THE BUILDING REVIEW APPROVAL ALL PRODUCT |
| | APPROVALS WERE GOING TO BE SUBMITTED LATER. THIS WAS |
| | BECAUSE THE PRODUCT APPROVAL SCHEDULE ON SHEET 3 OF 10 |
| | DIDN'T MATCH PRODUCT APPROVALS SUBMITTED. |
| | SUBMIT PRODUCT APPROVAL FOR: ENTRY DOORS, OVERHEAD |
| | GARAGE DOORS, GARAGE EXTERIOR SIDE DOORS. |
| | |
| | 4- CLARIFY WHY SUBMITTING MULLION PRODUCT APPROVAL. |
| | ACCORDING TO PLANS THERE ARE NOT MULLIONS. |
| | SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | 5- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| | NOTE: TO EXPEDITE THE REVIEW PROCESS AND AVOID |
| | CONFLICTS/DELAYS PLEASE PROVIDE A SINGLE PRODUCT |
| | APPROVAL REVIEW LETTER LISTING ALL THE PRODUCT |
| | APPROVALS. |
| | |
| | |
| | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| | THE REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| | QUESTIONS REGARDING THESE COMMENTS, |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | [email protected] |
| | |