Plan Review Notes
Plan Review Notes For Permit 21041212
Permit Number 21041212
Review Stop P
Sequence Number 1
Notes
Date Text
2021-05-11 11:48:32CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
 A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS
 REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW
 PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL
 PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST
 BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW
 APPROVAL.
  
 1.RE:A-400, A-001.02 AND A-001.03
 PER WPB FBC 107.2.1, COORDINATE AND RECONCILE A-400
 WITH A-001.02 AND A-001.03. PROVIDE A NOTE ON A-400 TO
 REFERENCE A-001.02 AND A-001.03 FOR ADA CLARIFICATIONS.
 A. A-001.02: THE WATER CLOSET SHALL BE POSITIONED WITH
 A WALL OR PARTITION TO THE REAR AND TO ONE SIDE. THE
 CENTERLINE OF THE WATER CLOSET SHALL BE 16 INCHES
 MINIMUM TO 18 INCHES MAXIMUM FROM THE SIDE WALL OR
 PARTITION PER FBC ACC 604.2. PER WPB FBC 107.2.1, NOTE
 MINIMUM AND MAXIMUM.
 B. A-001.02: THE REAR WALL GRAB BAR SHALL BE 36 INCHES
 LONG MINIMUM AND EXTEND FROM THE CENTERLINE OF THE
 WATER CLOSET 12 INCHES MINIMUM ON ONE SIDE AND 24
 INCHES MINIMUM ON THE OTHER SIDE PER FBC ACC 604.5.2.
 THIS IS THE REQUIREMENT. THE GRAB BAR SHALL BE 36
 INCHES MINIMUM. SHOW THE 12 INCHES MINIMUM ON ONE SIDE
 AND 24 INCHES MINIMUM ON THE OTHER SIDE. ADDITIONALLY,
 AS THE CENTER OF THE WATER CLOSET CAN FLUCTUATE 16
 INCHES MINIMUM TO 18 INCHES MAXIMUM FROM THE SIDE WALL
 THE SPACE BETWEEN THE SIDE WALL AND THE GRAB BAR SHALL
 BE 6 INCHES MAXIMUM, NOT 6 INCHES.
 C. A-400, DETAIL 1: THE SPACE BETWEEN THE SIDE WALL AND
 THE REAR GRAB BAR SHALL BE 6 INCHES MAXIMUM, NOT 6-1/2
 INCHES.
 D. A-400 AND A-001.01: PER FBC ACC 609.4, GRAB BARS
 SHALL BE INSTALLED IN A HORIZONTAL POSITION, 33 INCHES
 MINIMUM AND 36 INCHES MAXIMUM ABOVE THE FINISH FLOOR
 MEASURED TO THE TOP (NOT THE CENTER) OF THE GRIPPING
 SURFACE
 E. A-400: PER FBC 606.5 EXPOSED PIPES AND SURFACES.
 WATER SUPPLY & DRAINPIPES UNDER LAVATORIES AND SINKS
 SHALL BE INSULATED OR OTHERWISE CONFIGURED TO PROTECT
 AGAINST CONTACT. THIS IS ADDRESSED ON A-001.03 BUT
 NEEDS TO BE CLARIFIED ON A-400. AS A-400 APPEARS TO BE
 THE FINISH SCHEDULE, THE ARCHITECT MAY WANT TO PROVIDE
 A PROTECTIVE PANEL.
 F. A-400: MIRRORS LOCATED ABOVE LAVATORIES OR
 COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE OF
 THE "REFLECTING SURFACE" 40 INCHES MAXIMUM ABOVE THE
 FINISH FLOOR OR GROUND PER FBC ACC 603.3.
  
 2.PER WPB FBC 107.2.1, PROVIDE A SLAB REPAIR DETAIL.
 SHOW THE WIDTH OF THE REPAIR, THE MINIMUM THICKNESS OF
 THE CONCRETE TO BE REPLACED, AND THE PSI OF THE
 CONCRETE. SHOW THE SIZE AND LENGTH OF THE DOWELS, THE
 MINIMUM EMBEDMENT DEPTH INTO THE EXISTING SLAB, THE
 ANCHORING MATERIAL FOR THE DOWELS AND THE SPACING OF
 THE DOWELS ON CENTER. THE REPAIR SHALL ALSO INCLUDE
 TERMITE TREATMENT OF THE SOIL AND THE REQUIRED VAPOR
 BARRIER OVER WELL-COMPACTED SOIL. A COPY OF THE TERMITE
 CERTIFICATE SHALL BE ONSITE FOR A FINAL INSPECTION.
  
 3.THERE IS NOT A LIFE SAFETY PLAN. PER WPB FBC 107.2.1,
 PROVIDE AND INDICATE SMOKE/FIRE RATED WALLS. IF
 PLUMBING PIPING PASSES THROUGH ANY RATED WALLS, THEN
 PROVIDE DETAILS/ASSEMBLIES FOR SAID PENETRATIONS
 COMPLYING WITH THE REQUIREMENTS OF FBC CHAPTER 7.
  
 4.PLAN SHEET M-000, PLUMBING SECTION 15400, B. DOMESTIC
 WATER, (2) PIPE MATERIAL; PER WPB FBC 107.2.1, REPLACE
 THE WORDS "FITTINGS, JOINTED WITH TIN-ANTIMONY (95/5)
 SOLDER" WITH THE WORDS "FITTINGS. PER FBC PL 605.12.3,
 A FLUX CONFORMING TO ASTM B813 SHALL BE APPLIED. THE
 JOINT SHALL BE SOLDERED WITH A SOLDER CONFORMING TO
 ASTM B32. THE JOINING OF WATER SUPPLY PIPING SHALL BE
 MADE WITH LEAD-FREE SOLDER AND FLUXES. ALL COMPONENTS
 IN THE SYSTEM SHALL BE LEAD FREE. LEAD FREE SHALL MEAN
 A CHEMICAL COMPOSITION EQUAL TO OR LESS THAN
 0.2-PERCENT LEAD."
  
 5.PER WPB FBC 107.2.1, PROVIDE DETAIL FOR TP-1 MOUNTED
 IN THE WALL WITH ACCESS PANEL (PROVIDE SPEC/DESCRIPTION
 FOR PANEL); INCLUDE PIPING AND VALVE(S).
  
 6.PER FBC PL 606.1(5) PROVIDE FULL OPEN VALVES ON THE
 TOP OF EVERY WATER DOWN-FEED PIPE IN OCCUPANCIES OTHER
 THAN ONE- AND TWO-FAMILY RESIDENTIAL OCCUPANCIES.
  
 7.TO PROVIDE SUFFICIENT HOT WATER FLOW TO THE
 FIXTURE(S) AS REQUIRED BY FBC PL 604.1 AND 604.3,
 PROVIDE A BALANCING VALVE WITH CHECK VALVE IN THE NEW
 HOT WATER RETURN LINE. PER WPB FBC 107.2.1, PROVIDE A
 DETAIL, LOCATION, AND SPECIFICATION FOR BALANCING VALVE
 AND CHECK VALVE WHERE CONNECTING HOT WATER RETURN TO
 THE EXISTING RECIRCULATING SYSTEM. PROVIDE ACCESS PANEL
 IF LOCATED IN A HARD CEILING.
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  
 21041212 701 S ROSEMARY AVE # 101
  