2022-03-17 10:59:19FIRE REVIEW COMMENTS:
 PROVIDE A SITE PLAN AND INCLUDE ACCESS GATE LOCATIONS
 AND GATE DIMENSIONS TO PROVIDE A CLEAR WIDTH FOR FIRE
 APPARATUS ACCESS OF NOT LESS THAN 20 FEET IN WIDTH.
 NFPA 1, FIRE CODE, 18.2.3.4