2021-05-05 10:29:16WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21041156
 ADD: 1801 S. FLAGLER DR. # 101
 CONT: COUNIHAN CONSTRUCTION LLC
 TEL: 561-722-6266
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. MAY 05TH/2021
 ACTION: DENIED
 1) SHEET A-1 SHOWS THE REMOVAL & REPLACEMENT OF (2)
 SLIDING DOORS AND (3) WINDOW OPENINGS, ONE WINDOW WITH
 A VERTICAL MULLION. THERE IS A KEY FLOOR PLAN SHOWING
 THIS IS AN END UNIT IN A WALL ZONE 5. THE PLAN STATES
 HE WORST CASE ZONE 5 ALL OPENINGS WINDOWS AND DOORS AND
 LIST +60.7/ - 106.9 PSF. THE PLAN DOES NOT PROVIDE IF
 THESE PRESSURES ARE IN VULT OR VASD. THE PLAN ALSO
 FAILS TO INDICATE HOW THESE PRESSURES WERE DERIVED.
 2020 FBC-B 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
  
 1.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR AND NOMINAL DESIGN WIND SPEED, VASD, AS
 DETERMINED IN ACCORDANCE WITH SECTION 1609.3.1.
  
 1.2. RISK CATEGORY.
  
 1.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2.
 HEIGHT AND EXPOSURE. ASCE 7-16 TABLE 30.3.1.
  
 1.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 1.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENTS AND CLADDING MATERIALS SPECIFICALLY DESIGNED
 BY THE REGISTERED DESIGN PROFESSIONAL RESPONSIBLE FOR
 THE DESIGN OF THE STRUCTURE, PSF.
  
 1.6. TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING. ASCE 7-10 TABLE 30.3.1. 1609.3.1 WIND SPEED
 CONVERSION VULT TO VASD.
  
 2) SHEET A-1. . THE PLAN STATES HE WORST CASE ZONE 5
 ALL OPENINGS WINDOWS & DOORS AND LIST +60.7/ - 106.9
 PSF. WHEN VIEWING EACH OPENING THE 3 WINDOWS ARE SHOWN
 TO BE +80/ -196.5 PSF AND THE SLIDING DOORS BOTH WITH A
 PRESSURE OF +73.3/ -115 PSF. THEN IN THE BREAKFAST ROOM
 HERE IS A SECOND SET OF PRESSURES +65.9/ -120.8 PSF.
 DISCREPANCY IN PRESSURES. 107.2.1.2. ADDITIONAL
 INFORMATION IS REQUIRED.
  
 3) IN DETERMINING WALL ZONE 5, A= 10% OF LEAST
 HORIZONTAL DIMENSION OR 40 % OF THE MEAN ROOF HEIGHT,
 WHICHEVER IS SMALLER, BUT NOT LESS THAN 4% OF THE LEAST
 HORIZONTAL DIMENSION. ASCE 7-16 CHAPTER 30 COMPONENTS
 AND CLADDING.
  
 4) PLEASE NOTE THAT MIAMI-DADE NOA 20-0722.20 360
 ALUMINUM SINGLE HUNG WINDOW LMI WAS SUBMITTED TWICE, NO
 PRODUCT APPROVAL WAS SUBMITTED FOR THE SLIDING GLASS
 DOORS.
 COMPONENTS & CLADDING. 2020 FBC-B 1609.1.2 PROTECTION
 OF OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING.
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE
 CODE 61G20-3.005, RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS, SLIDING GLASS DOORS.
  
 5) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE
 PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF
 RECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING,
 TRACK HEIGHT FOR SLIDING GLASS DOORS, MULLION SIZE,
 LENGTH IF UNREINFORCED OR REINFORCED INFORMATION IF
 REQUIRED, ATTACHMENTS AND ASSOCIATE PRESSURES FOR EACH
 OPENING SIZE. 2020 FBC-B 1405.13.1 INSTALLATION.
 WINDOWS AND DOORS SHALL BE INSTALLED IN ACCORDANCE WITH
 APPROVED MANUFACTURER?S INSTRUCTIONS. FASTENER SIZE AND
 SPACING SHALL BE PROVIDED IN SUCH INSTRUCTIONS AND
 SHALL BE CALCULATED BASED ON MAXIMUM LOADS AND SPACING
 USED IN THE TESTS.
  
 6) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/
 RETIRED.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  