Plan Review Notes
Plan Review Notes For Permit 21041115
Permit Number 21041115
Review Stop B
Sequence Number 1
Notes
Date Text
2021-04-22 06:42:07PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 BUILDING REVIEW DENIED:
  
 1) THE SUBMITTED STRAPPING INFORMATION IS NOT CLEAR.
 PROVIDE A STRUCTURAL CONNECTION DETAIL FOR THE TENT
 FRAMING AND A TIE DOWN DETAIL WITH DESIGN CALCULATIONS.
 2) THE WINDLOAD INFORMATION AND THE UP TO DATE FLORIDA
 BUILDING CODE CYCLE (FBC B 2020 7TH EDITION) NEEDS TO
 BE INDICATED ON THE SUBMITTED INFORMATION.
 3) THE SUBMITTED ENGINEERING MUST BE DIGITALLY
 SIGNED(THIRD PARTY VERIFIED) OR HAVE ORIGINAL
 SIGNATURES & SEALS BY THE DESIGN PROFESSIONAL.
 4) PROVIDE A LAYOUT SHEET INCLUDING THE LOCATION OF
 RESTROOMS. THE ACCESSIBLE RESTROOMS SHALL BE LOCATED
 WITHIN 500' OF TENTS.
 5) IF THE TENT IS COVERED ON THE SIDES, PLEASE SHOW
 LOCATION OF DOOR OPENINGS AND EGRESS PATH.
  
  
  
  