| 2021-05-18 23:36:49 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. NO EQUIPMENT GROUND SHOWN FROM SERVICE DISCONNECTS |
| | TO INTERIOR PANELS. NEC 250.4A3 |
| | |
| | 2. RISER ONLY SHOWS ONE METER AND DISC BUT PLANS SHOWS |
| | DISC/METER FOR EACH UNIT. PROVIDE CORRECTION. FBC |
| | 107.2.1 |
| | |
| | 3. FOR A ONE FAMILY DWELLING AND EACH UNIT OF A |
| | TWO-FAMILY DWELLING THAT IS AT GRADE LEVEL, AT LEAST |
| | ONE RECEPTACLE OUTLET READILY ACCESSIBLE FROM GRADE AND |
| | NOT MORE THAN 2.0 M (6.5 FT) ABOVE GRADE LEVEL SHALL BE |
| | INSTALLED AT THE FRONT AND BACK OF THE DWELLING. |
| | PROVIDE CORRECTION. NEC 210.52(E)(1) FBC RE E3901.7 |
| | |
| | 4. NO ARC-FAULT PROTECTION SHOWN. PROVIDE CORRECTION |
| | PER NEC 210.12 |
| | |
| | 5. SMOKE ALARMS MUST BE 3FT FROM BEDROOMS NFPA 72 |
| | 29.8.3.4 #6 |
| | |
| | 6. NO WORKING CLEARANCE FOR AC CONDENSOR DISCONNECTS |
| | NEC 110.26A1 |
| | |
| | 7. TAMPERPROOF RECEPTACLES REQUIRED NEC 406.12 |
| | |
| | 8. GEC TO CONCRETE ENCASED ELECTRODE IS TO BE MINIMUM |
| | #4 CU NEC 250.66B |
| | |
| | |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | CODES IN EFFECT: |
| | |
| | HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B |
| | UILDING-PERMIT-FORMS |
| | |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2020 7TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| | 7TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |