| 2021-09-17 13:58:23 | NEW SINGLE FAMILY RESIDENCE (R3) THIRD BUILDING REVIEW |
| | COMMENTS |
| | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| | PERMIT #21041103 |
| | |
| | 1- OK |
| | |
| | 2- OK |
| | |
| | 3- OK |
| | |
| | 4- SHEET 4-4: |
| | REVISE/CLARIFY THE ROOF SHEATHING NOTE NEXT TO THE ROOF |
| | PLAN UNDER THE COMPONENT AND CLADDING PRESSURE ZONES |
| | TABLE. THIS NOTE CONTRADICTS THE NAIL SPACING |
| | SPECIFICATIONS SHOWN ON THE COMPONENT AND CLADDING |
| | PRESSURE ZONES TABLE. REVISE AS REQUIRED. SEC. 107.2.1 |
| | CITY AMENDMENTS. |
| | |
| | RESPONSE: |
| | REPEAT COMMENT. NOT ADDRESSED. |
| | |
| | 5- OK |
| | |
| | 6- REVISE ENERGY CALCULATIONS SUBMITTED: |
| | A)ENERGY CALCULATIONS FORM IS REQUIRED TO BE CERTIFIED |
| | AT THE BOTTOM OF THE FORM BY THE OWNER, THE OWNER'S |
| | ARCHITECT OR OTHER AUTHORIZED AGENT LEGALLY DESIGNED BY |
| | THE OWNER PRIOR TO RECEIVE THE PERMIT AS REQUIRED BY |
| | SEC. R103.1.1.2 FBC-ENERGY CONSERVATION. |
| | |
| | RESPONSE: |
| | REPEAT COMMENT. NOT ADDRESSED. |
| | |
| | B)PROVIDE COMPLETE AND CORRECT INFORMATION ON TOP OF |
| | FORM. PROVIDE CORRECT OWNER'S NAME, PROVIDE NAME OF |
| | BUILDER, PERMITTING OFFICE AND JURISDICTION NUMBER |
| | (THIS JURISDICTION IS 604700). |
| | SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| | |
| | RESPONSE: |
| | REPEAT COMMENT. NOT ADDRESSED. |
| | |
| | C)WINDOWS INFORMATION ON PAGE 3 OF 4 IS INCOMPLETE. |
| | MISSING THE MASTER BEDROOM WINDOW. SEC. R101.5.1.1.2 |
| | FBC-ENERGY CONSERVATION. |
| | |
| | D)BUILDER TO SIGN AND COMPLETE THE ENERGY PERFORMANCE |
| | LEVEL (EPL) DISPLAY CARD. SEC. R405.4.3 FBC- ENERGY |
| | CONSERVATION. |
| | |
| | RESPONSE: |
| | REPEAT COMMENT. NOT ADDRESSED. |
| | |
| | NEW COMMENTS: |
| | (NOTE: THIS IS THE FIRST REVIEW ON THE PLANS FOR THE |
| | MAIN HOUSE. THE FIRST REVIEW WAS BASED ONLY ON PLANS |
| | SUBMITTED FOR THE MOTHER-IN-LAW HOUSE). |
| | |
| | 7- CLEARLY SPECIFY SIZE OF SINGLE HUNG EGRESS BEDROOM |
| | WINDOWS (WIDTH AND HEIGHT) AS SPECIFIED ON THE |
| | MOTHER-IN-LAW HOUSE PLANS. PLANS ONLY SPECIFY 25SH |
| | EGRESS BUT NO SIZE. SEC. R310.2.1 FBC-RESIDENTIAL. |
| | |
| | NOTE: |
| | A)LANDSCAPE UNDER A SEPARATE PERMIT. PLANS WERE |
| | DELETED. |
| | |
| | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| | THE REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |