| Plan Review Notes For Permit 21041095 |
| Permit Number |
21041095 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-04-30 16:27:08 | PLAN REVIEW BUILDING | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | PLANS EXAMINER PX3169 1&2 FAMILY - SFP306 | | | INSPECTOR BN4338 | | | BUILDING OFFICIAL BU1635 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | CODES IN EFFECT: | | | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | 2017 NEC | | | | | | 1ST REVIEW | | | | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1. PROVIDE A WINDOW SCHEDULE. REFERENCE LOCATION TO | | | PLAN. INCLUDE ROUGH OPENING (AREA OF OPENING) AND | | | DESIGN PRESSURE OF EACH OPENING. | | | YOU MAY PLACE THIS INFORMATION ON YOUR PLAN. | | | 1603.1.4WIND DESIGN DATA. | | | | | | 2. ASCE 7-10 HAS EXPIRED. PROVIDE WIND LOADS PER ASCE | | | 7-16. WIND LOADS SHALL BE PREPARED BY A DESIGN | | | PROFESSIONAL. | | | | | | 3. DESIGNER (CONTRACTOR) SHALL SIGN PLAN. SEE SIGNATURE | | | REVIEW COMMENTS. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
|