| Plan Review Notes For Permit 21041092 |
| Permit Number |
21041092 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2021-10-13 14:34:49 | PLEASE PROVIDE A MECHANICAL DRAWING SHOWING THE EXHAUST | | | FAN, EXHAUST DUCT AND TERMINATION LOCATION OF THE | | | EXHAUST FOR THIS NEW BATHROOM. | | | PLEASE SHOW THE SUPPLY AIR DUCTWORK AND GRILLE FOR THIS | | | NEW BATHROOM. | | | THE A SHEETS HAVE A DETAIL OF A CONDENSING UNIT AND A | | | SLAB. REMOVE THIS DETAIL IF THERE WILL NOT BE A NEW | | | MECHANICAL SYSTEM INSTALLED AT THIS LOCATION. IF THERE | | | IS GOING TO BE NEW MECHANICAL SYSTEM INSTALLED AT THIS | | | LOCATION THEN PROVIDE A MECHANICAL DRAWING SHOWING THIS | | | AND THE UNIT INFORMATION. FBC 107.2.1 | | | |
|