| 2021-05-27 14:51:04 | REVISION |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected] |
| | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| | AMENDMENTS |
| | |
| | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 |
| | 1) DRAWING A6.0 APPEARS TO BE A PREVIOUS PLAN THAT |
| | SHOWS DOOR PRODUCT APPROVALS WHICH WERE NOT APPROVED. |
| | 2) PLEASE SHOW STAIR HANDRAIL EXTENSIONS TOP AND BOTTOM |
| | TO COMPLY WITH FBC 1014.6 HANDRAIL EXTENSIONS. |
| | HANDRAILS SHALL RETURN TO A WALL, GUARD OR THE WALKING |
| | SURFACE OR SHALL BE CONTINUOUS TO THE HANDRAIL OF AN |
| | ADJACENT FLIGHT OF STAIRS OR RAMP RUN. WHERE HANDRAILS |
| | ARE NOT CONTINUOUS BETWEEN FLIGHTS, THE HANDRAILS SHALL |
| | EXTEND HORIZONTALLY NOT LESS THAN 12 INCHES (305 MM) |
| | BEYOND THE TOP RISER AND CONTINUE TO SLOPE FOR THE |
| | DEPTH OF ONE TREAD BEYOND THE BOTTOM RISER. AT RAMPS |
| | WHERE HANDRAILS ARE NOT CONTINUOUS BETWEEN RUNS, THE |
| | HANDRAILS SHALL EXTEND HORIZONTALLY ABOVE THE LANDING |
| | 12 INCHES (305 MM) MINIMUM BEYOND THE TOP AND BOTTOM OF |
| | RAMP RUNS. THE EXTENSIONS OF HANDRAILS SHALL BE IN THE |
| | SAME DIRECTION OF THE FLIGHTS OF STAIRS AT STAIRWAYS |
| | AND THE RAMP RUNS AT RAMPS. |
| | 3) DRAWING A2.0 APPEARS TO BE A PREVIOUS PLAN WHICH |
| | SHOWS EXTERIOR CORRIDOR BLOCKED WITH DOORS THAT OPEN |
| | OUT BETWEEN THE UNITS FBC 1005.7.1 DOORS. |
| | DOORS, WHEN FULLY OPENED, SHALL NOT REDUCE THE REQUIRED |
| | WIDTH BY MORE THAN 7 INCHES (178 MM). DOORS IN ANY |
| | POSITION SHALL NOT REDUCE THE REQUIRED WIDTH BY MORE |
| | THAN ONE-HALF. |