| Date |
Text |
| 2023-03-02 13:38:08 | RESIDENTIAL(R3) ADDITION, ALTERATION BUILDING REVIEW |
| | COMMENTS |
| | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| | PERMIT # 21041010 |
| | 101 GREYMON DR |
| | |
| | |
| | PROVISO NOTE: |
| | BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO |
| | MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER |
| | THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID |
| | CONFLICTS/DELAYS. REVISION FEES APPLY (EXCEPT FOR |
| | PRODUCT APPROVALS DEFERRED SUBMITTAL). |
| | |
| | ***IMPORTANT**** |
| | CONTRACTOR TO ADVICE IF PROVISO OPTION IS PREFERRED AT |
| | THIS TIME OR IF RE-SUBMITTING REQUIRED INFORMATION |
| | BEFORE PERMIT ISSUANCE. |
| | |
| | |
| | PREVIOUS COMMENT: |
| | (2)-PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. |
| | 1106 FBC-EXISTING BUILDING AND SEC. R101.5 FBC-ENERGY |
| | CONSERVATION. |
| | NOTE: PLEASE MAKE SURE FORMS ARE PROPERLY SIGNED BY ALL |
| | REQUIRED PARTIES AND IS COORDINATED WITH PLANS TO AVOID |
| | CONFLICTS/DELAYS. |
| | |
| | RESPONSE |
| | REVISE ENERGY CALCULATIONS SUBMITTED: |
| | (A)PROVIDE COMPLETE INFORMATION ON TOP OF FORM, |
| | INCLUDING OWNER'S NAME, BUILDER'S NAME, PERMIT OFFICE |
| | AND JURISDICTION NUMBER (THIS JURISDICTION IS 604700). |
| | SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| | |
| | (B)REVISE ITEM #1 ON PAGE 1. THIS IS NOT NEW |
| | CONSTRUCTION, THIS IS EXISTING. SEC. R101.5.1.1.2 |
| | FBC-ENERGY CONSERVATION. |
| | |
| | (C)REVISE ITEM #11 ON PAGE 1. CEILING INSULATION IS |
| | REQUIRED. SEC. R405.2.1 FBC-ENERGY CONSERVATION. |
| | |
| | (D)SPECIFY HOT WATER SYSTEM INFORMATION AS REQUIRED BY |
| | SEC. R403.5.6 FBC-ENERGY CONSERVATION. |
| | |
| | (E)ITEM #16 ON PAGE 1 IS TAKING THE CEILING FAN CREDIT. |
| | PLANS DON'T SHOW CEILING FANS. REVISE AS REQUIRED TO |
| | MATCH PLANS OR REVISE PLANS SHOWING THE CEILING FAN |
| | SIZES AND NUMBER OF FANS REQUIRED FOR EACH ROOM BASED |
| | ON THE SIZE AS REQUIRED BY TABLE R405.7.6 FBC-ENERGY |
| | CONSERVATION. |
| | |
| | (F)REVISE DOORS INFORMATION ON PAGE 3. ACCORDING TO |
| | WINDOW/DOOR REPLACEMENT PERMIT #22031558 AND #22031203 |
| | THERE ARE NOT WOOD DOORS. PRODUCT APPROVALS SUBMITTED |
| | FOR THESE PERMITS ARE FOR GLAZED DOORS. |
| | NOTE: GLAZING IN DOORS NEEDS TO BE INCLUDED IN THE |
| | WINDOW GLAZING AREA. SEE SEC. R405.5.3 FBC-ENERGY |
| | CONSERVATION) |
| | |
| | (G)REVISE THE WINDOWS INFORMATION ON PAGE 3 TO MATCH |
| | PLANS. REVISE AREA AND NUMBER OF WINDOWS TO MATCH |
| | PLANS. ALSO, INCLUDE DOORS WITH GLAZING. SEE COMMENT |
| | ABOVE. |
| | SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| | |
| | 5- DESIGNER OF RECORD NEEDS TO SPECIFY COMPLETE DESIGN |
| | CRITERIA: |
| | PREVIOUS COMMENT: |
| | D)COMPONENTS AND CLADDING DESIGN PRESSURES (DOORS AND |
| | WINDOWS) |
| | SEC. R301.2.1 FBC RESIDENTIAL. |
| | |
| | RESPONSE: |
| | BUILDING EXPOSURE WAS REVISED TO D. THE DESIGN |
| | PRESSURES SPECIFIED ON THE NEW WIND PRESSURE CHART ON |
| | SHEET S100 SEEM TO BE TOO LOW COMPARED TO TABLE |
| | R301.2(2)FBC-RESIDENTIAL AND TABLE |
| | R301.2(3)FBC-RESIDENTIAL FOR THE HEIGHT AND EXPOSURE |
| | ADJUSTMENT TO EXPOSURE D. REVISE DESIGN PRESSURES AS |
| | REQUIRED OR ENGINEER TO PROVIDE ACTUAL CALCULATIONS. |
| | SEC. 107.2.1.2 CITY AMENDMENTS. |
| | |
| | 20- PROPOSED PLAN ON SHEET S102: |
| | PREVIOUS COMMENT: |
| | D)THIS IS A CHANGE OF USE FROM GARAGE TO LIVABLE SPACE. |
| | TYPICALLY, GARAGES ARE BUILT WITHOUT A FLOOR VAPOR |
| | BARRIER. ENGINEER OF RECORD TO PROVIDE SPECIFICATIONS |
| | FOR THE CONCRETE SLAB VAPOR BARRIER AS REQUIRED BY SEC. |
| | R506.2.3 FBC-RESIDENTIAL. |
| | ALSO, ENGINEER OF RECORD DOESN'T PROVIDE ANY |
| | INFORMATION OF HOW THE GARAGE SLAB IS RAISED TO THE |
| | EXISTING HOUSE LEVEL AS SHOWN ON SHEET A2.2. PROVIDE |
| | COMPLETE INFORMATION. SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | RESPONSE: |
| | NO ADDRESSED. INFORMATION NO PROVIDED AND FOUNDATION |
| | PLAN ON SHEET S102 STAYS "EXISTING SLAB TO REMAIN (NO |
| | WORK)". REQUESTED INFORMATION WAS NOT PROVIDED. |
| | |
| | 21- SHEET S103: |
| | PREVIOUS COMMENT: |
| | B)SECTION 1: ENGINEER TO SPECIFY LENGTH OF #9 SCREWS. |
| | HOW MUCH EMBEDMENT IS REQUIRED INTO THE 4X2 BATTEN?. |
| | SEC. 107.2.1 CITY AMENDMENTS. SEC. R301.2.1 |
| | FBC-RESIDENTIAL. |
| | |
| | RESPONSE: |
| | DETAIL WAS REVISED BUT NOW IT DOESN'T SPECIFY HOW IS |
| | THE 2X P.T. RAFTER ATTACHED TO THE BEAM? PROVIDE |
| | SPECIFICATIONS. SEC. R301.1 FBC-RESIDENTIAL. |
| | |
| | PREVIOUS COMMENT: |
| | 22)SHEET S104: ENGINEER TO PROVIDE SPECIFICATIONS FOR |
| | WELDING AT THE BASE AND TOP PLATES OF STEEL COLUMNS. |
| | SEC. 107.2.1 CITY AMENDMENTS. SEC. R301 |
| | FBC-RESIDENTIAL. |
| | |
| | RESPONSE: |
| | REPEAT COMMENT. INFORMATION ON SHEET S104 WAS NOT |
| | REVISED AND NOW IT IS NOT CLEAR WHERE THE STEEL COLUMNS |
| | AND BEAMS ARE GOING TO BE INSTALLED. |
| | |
| | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| | THE REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| | QUESTIONS REGARDING THESE COMMENTS, |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | [email protected] |