2022-10-04 10:28:242ND REVIEW FMC
 PERMIT: 21041010
  
 CODES IN EFFECT: 2020
  
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
  
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE SUBMITTED MECHANICAL EQUIPMENT SIZING
 CALCULATIONS CALL FOR A 3.3-TON SYSTEM. SHEET M-1 SHOWS
 THIS MECHANICAL SYSTEM IS FOR THE ENTIRE HOME. SHEET
 M-0 INDICATE THE AHU IS A 5-TON SYSTEM. PLEASE SHOW
 THAT THE NEW SYSTEM MEETS THE 1.15 TIMES MAX LIMIT
 REQUIRED IN THE FLORIDA ENERGY CODE. FEC R403.7.1.2;
 FRC M1401.3
  
 2) SHEET M-1 INDICATES THAT THE DRYER EXHAUST WILL
 TERMINATE ON THE ROOF. SHEET M-2 PITCHED ROOF CAP
 DETAIL INDICATES AN INSECT SCREEN IN THE EXHAUST
 TERMINATION. PLEASE REMOVE THE SCREEN FROM THIS DETAIL
 OR ADD A NOTE THAT THE DRYER EXHAUST WILL NOT HAVE A
 SCREEN AT THE DUCT TERMINATION. FRC M1502.3
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  