Plan Review Notes
Plan Review Notes For Permit 21041010
Permit Number 21041010
Review Stop G
Sequence Number 2
Notes
Date Text
2022-10-05 10:51:151ST GAS REVIEW
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
  
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2020 FRC G2439.5 (614.6) MAKEUP AIR FOR DRYER.
 PLEASE SHOW THE CALCULATION FOR THE REQUIREMENT OR
 EXCEPTION TO THE NEED FOR MAKE-UP AIR FOR THE DRYER.
  
 2. 2020 FRC G2415.17.1 (404.17.1) LIMITATIONS - PLASTIC
 GAS LINE SHALL BE INSTALLED OUTDOORS UNDERGROUND ONLY.
 IT SHALL NOT BE USED WITHIN OR UNDER ANY BUILDING.
 PLEASE FIND ANOTHER MATERIAL TO GET INTO THE RANGE.
  
 3. 2020 FRC G2415.14.1 (404.14.1) CONDUIT WITH ONE END
 TERMINATING OUTDOORS - THE SLEEVE (CONDUIT) MUST
 TERMINATE IN AN "OCCUPIABLE" PORTION OF THE BUILDING.
 PLEASE CHOSE A LOCATION THAT IS "OCCUPIABLE". (INSIDE A
 CABINET COULD BE CONSIDERED OCCUPIABLE) IT CANNOT
 TERMINATE IN A CONCEALED LOCATION AND CANNOT BE LOCATED
 BEHIND AN ACCESS PANEL. SHOW THE DETAILS THAT COMPLY
 WITH ALL THE ASPECTS OF THE SLEEVE TERMINATION INDOORS
 AND OUTDOORS, AND SEALING. THE SLEEVE WITH ONE END
 INDOORS WOULD NOT BE SEALED ON THE EXTERIOR, BUT WOULD
 BE DESIGNED TO PREVENT RODENTS FROM INTRUDING.
  
 4. 2020 FRC G2413.3 (402.3) SIZING - ACCORDING TO THE
 SIZE CHART YOU'VE REFERENCED, USING THE LONGEST RUN
 METHOD, YOU WOULD NEED 1 1/4" BETWEEN THE METER AND
 WATER HEATER. 3/4" BETWEEN THE METER AND BBQ, AND 3/4"
 TO THE COOKTOP. YOU SHOULD LOOK AT THE PRESSURE DROP
 (.3 IN W.C.) AND RECONSIDER.
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  