| 2022-10-05 10:51:15 | 1ST GAS REVIEW |
| | |
| | V7 FPC - 2020 FLORIDA PLUMBING CODE |
| | V7 FGC - 2020 FLORIDA FUEL GAS |
| | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE |
| | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE |
| | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE |
| | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION |
| | |
| | 2021 F.S. - 2021 FLORIDA STATUTES |
| | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE |
| | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE |
| | FBC CHAPTER 1 |
| | |
| | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED |
| | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. |
| | |
| | 1. 2020 FRC G2439.5 (614.6) MAKEUP AIR FOR DRYER. |
| | PLEASE SHOW THE CALCULATION FOR THE REQUIREMENT OR |
| | EXCEPTION TO THE NEED FOR MAKE-UP AIR FOR THE DRYER. |
| | |
| | 2. 2020 FRC G2415.17.1 (404.17.1) LIMITATIONS - PLASTIC |
| | GAS LINE SHALL BE INSTALLED OUTDOORS UNDERGROUND ONLY. |
| | IT SHALL NOT BE USED WITHIN OR UNDER ANY BUILDING. |
| | PLEASE FIND ANOTHER MATERIAL TO GET INTO THE RANGE. |
| | |
| | 3. 2020 FRC G2415.14.1 (404.14.1) CONDUIT WITH ONE END |
| | TERMINATING OUTDOORS - THE SLEEVE (CONDUIT) MUST |
| | TERMINATE IN AN "OCCUPIABLE" PORTION OF THE BUILDING. |
| | PLEASE CHOSE A LOCATION THAT IS "OCCUPIABLE". (INSIDE A |
| | CABINET COULD BE CONSIDERED OCCUPIABLE) IT CANNOT |
| | TERMINATE IN A CONCEALED LOCATION AND CANNOT BE LOCATED |
| | BEHIND AN ACCESS PANEL. SHOW THE DETAILS THAT COMPLY |
| | WITH ALL THE ASPECTS OF THE SLEEVE TERMINATION INDOORS |
| | AND OUTDOORS, AND SEALING. THE SLEEVE WITH ONE END |
| | INDOORS WOULD NOT BE SEALED ON THE EXTERIOR, BUT WOULD |
| | BE DESIGNED TO PREVENT RODENTS FROM INTRUDING. |
| | |
| | 4. 2020 FRC G2413.3 (402.3) SIZING - ACCORDING TO THE |
| | SIZE CHART YOU'VE REFERENCED, USING THE LONGEST RUN |
| | METHOD, YOU WOULD NEED 1 1/4" BETWEEN THE METER AND |
| | WATER HEATER. 3/4" BETWEEN THE METER AND BBQ, AND 3/4" |
| | TO THE COOKTOP. YOU SHOULD LOOK AT THE PRESSURE DROP |
| | (.3 IN W.C.) AND RECONSIDER. |
| | |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |
| | |
| | RYAN W. BROWN |
| | CHIEF PLUMBING INSPECTOR |